Schedule Viewer
Last schedule upload: D3-R25005-00-RPL06 — 6139 activities — 04/16/2026 08:19 AM CT
RPL10 - GC LIVE SCHEDULE - Data Date 20260412.xer
· Uploaded Apr 16, 2026 12:51 PM
· 8408 activities
Experimental
Auto-populate checklist dates from schedule:
100
Activities Shown
0
Completed
0
In Progress
1
Critical
| Activity ID | Activity Name | WBS | Status | Start | Finish | Dur (d) | Rem (d) | % Comp | Float (d) |
|---|---|---|---|---|---|---|---|---|---|
RPL10.INT.EF2.01580 |
RPL10.Interior.EF2 - Final Clean | Tie-Ins | Not Started | 07/09/26 | 07/14/26 | 5.0 | 5.0 |
|
168.8 |
RPL10.INT.NS1.01780 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Install Vesda / FA | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/09/26 | 08/05/26 | 25.0 | 25.0 |
|
21.2 |
RPL10.INT.NS1.01790 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Install FW | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/09/26 | 08/05/26 | 25.0 | 25.0 |
|
15.0 |
RPL10.INT.NS1.02280 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Install TW | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/09/26 | 08/05/26 | 25.0 | 25.0 |
|
15.0 |
RPL10.INT.NS1.02800 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Install Duct (MES Side) | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/09/26 | 08/05/26 | 25.0 | 25.0 |
|
15.0 |
RPL10.INT.NS3.01920 |
RPL10.Interior.NS3 - Control Fault Domain 6 SQ12.2 - Install LV Side Aisle HAC Busway | LV Side Tie-ins | Not Started | 07/09/26 | 07/14/26 | 5.0 | 5.0 |
|
226.2 |
RPL10.INT.SSB.02960 |
RPL10.Interior.SSB - Loading Dock and Storage - Install Flooring | Loading Dock and Storage | Not Started | 07/09/26 | 07/15/26 | 6.2 | 6.2 |
|
146.2 |
RPL10.W3B.FE.011401 |
RPL10.Conn EF1F<>NS1.CFD5 (P2-3) Pull Fiber Trunk (288F) [EF<>JXSW] | EF1F<>NS1.2 (P2-3) [EF<>JXSW] | Not Started | 07/09/26 | 07/14/26 | 5.0 | 5.0 |
|
35.0 |
RPL10.W3B.FE.011881 |
RPL10.Conn EF2B<>NS1.CFD5 (P1-4) Install Fiber Trunk (288F) [EF<>JXSW] | EF2B<>NS1.2 (P1-4) [EF<>JXSW] | Not Started | 07/09/26 | 07/13/26 | 3.8 | 3.8 |
|
21.2 |
RPL10.W3B.FE.013161 |
RPL10.Conn EF1F<>NS1.CFD6 (P2-3) Test Fiber Trunk (384F) [EF<>SSW] | EF1F<>NS1.1 (P2-3) [EF<>SSW] | Not Started | 07/09/26 | 07/10/26 | 2.5 | 2.5 |
|
41.2 |
RPL10.WP3B.FE.01160 |
RPL10.Conn EF1F<>NS1.CFD5 (P2-3) Pull/Install/Test - WBS Summary | EF1F<>NS1.2 (P2-3) [EF<>JXSW] | Not Started | 07/09/26 | 08/07/26 | 27.5 | 27.5 |
|
33.8 |
RPL10.WP4.01340 |
RPL10.Conn NS1.CFD5.15 Pull Duplex Jumper (LC<>LC) [MA<>JXSW] | Pull Duplex Jumper [MA<>JXSW] | Not Started | 07/09/26 | 07/13/26 | 3.8 | 3.8 |
|
143.8 |
RPL10.INT.NS3.01940 |
RPL10.Interior.NS3 - Control Fault Domain 6 SQ12.2 - Install LV Side Aisle Cable Tray | LV Side Tie-ins | Not Started | 07/10/26 | 07/15/26 | 5.0 | 5.0 |
|
238.8 |
RPL10.INT.SSB.02600 |
RPL10.Interior.SSB - BoW - ACT - Close Up Inspection | Balance of Walls and OverHead | Not Started | 07/10/26 | 07/20/26 | 8.8 | 8.8 |
|
113.8 |
RPL10.W3B.FE.012391 |
RPL10.Conn EF1F<>NS2.CFD6 (P2-3) Install Fiber Trunk (384F) [EF<>SSW] | EF1F<>NS2.1 (P2-3) [EF<>SSW] | Not Started | 07/10/26 | 07/13/26 | 2.5 | 2.5 |
|
28.8 |
RPL10.W3B.FE.012791 |
RPL10.Conn EF1B<>NS2.CFD6 (P2-3) Test Fiber Trunk (384F) [EF<>SSW] | EF1B<>NS2.1 (P2-3) [EF<>SSW] | Not Started | 07/10/26 | 07/13/26 | 2.5 | 2.5 |
|
48.8 |
RPL10.WP3A.EF1F.1015 |
RPL10.Conn EF1F(LIU)<>EF1F(MBOX) Pull/Install/Test OSP Cabling (for RPL01) - P4 | EF1F<>EF1F | Not Started | 07/10/26 | 07/15/26 | 5.0 | 5.0 |
|
218.8 |
RPL10.WP3A.EF1F.1090 |
RPL10.Conn EF1F(LIU)<>EF1B(MBOX) Pull/Install/Test OSP Cabling (for RPL01) - P3 | EF1F<>EF1B | Not Started | 07/10/26 | 07/17/26 | 7.5 | 7.5 |
|
198.8 |
RPL10.WP4.027760 |
RPL10.Conn NS1.CFD4.48<>36-40 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/10/26 | 07/14/26 | 3.8 | 3.8 |
|
121.2 |
RPL10.WP4.027880 |
RPL10.Conn NS1.CFD3.48<>16-20 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/10/26 | 07/15/26 | 5.0 | 5.0 |
|
102.5 |
RPL10.WP4.028040 |
RPL10.Conn NS1.CFD2.48<>06-10 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/10/26 | 07/14/26 | 3.8 | 3.8 |
|
92.5 |
RPL.GF.D.G4640.XG |
Rack & Cabinets Complete - DHD - RPL6 | Give Milestones (XREFs) | Not Started | 07/13/26 | 07/13/26 | 0.0 | 0.0 |
|
410.0 |
RPL10.EY.EF1.01420 |
RPL10.EY.EF1 - Install RPL-2 FSP Interior Hilti Support & Cable Trays | Fiber Support Platform - RPL-2 | Not Started | 07/13/26 | 07/28/26 | 15.0 | 15.0 |
|
215.0 |
RPL10.INT.EF1.01570 |
RPL10.Interior.EF1 - L2 Checklist Completion | Tie-Ins | Not Started | 07/13/26 | 07/24/26 | 12.5 | 12.5 |
|
87.5 |
RPL10.INT.NS1.01730 |
RPL10.Interior.NS1 - Control Fault Domain 3 SQ4.1 - Install Mechanical Side Aisle Cable Tray | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/13/26 | 08/07/26 | 25.0 | 25.0 |
|
33.8 |
RPL10.INT.NS1.01760 |
RPL10.Interior.NS1 - Control Fault Domain 3 SQ4.1 - Install copper from GS.IDF to BMS and EPMS panels (UG from Center ID | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/13/26 | 08/07/26 | 25.0 | 25.0 |
|
15.0 |
RPL10.W3B.FE.011481 |
RPL10.Conn EF2F<>NS1.CFD5 (P1-4) Pull Fiber Trunk (288F) [EF<>JXSW] | EF2F<>NS1.2 (P1-4) [EF<>JXSW] | Not Started | 07/13/26 | 07/17/26 | 6.2 | 6.2 |
|
18.8 |
RPL10.WP2.GSIDF.1220 |
RPL10.Conn IDF Huts - (GSMDF to GSIDF) NS1 N12 WBS Summary | GSIDFN12 | Not Started | 07/13/26 | 08/12/26 | 28.8 | 28.8 |
|
413.8 |
RPL10.WP2.GSIDF.1240 |
RPL10.Conn GSIDFN12 Install Infrastructure (Racks, Waterfalls etc.) | Infrastructure | Not Started | 07/13/26 | 07/17/26 | 6.2 | 6.2 |
|
166.2 |
RPL10.WP3B.FE.01140 |
RPL10.Conn EF2F<>NS1.CFD5 (P1-4) Pull/Install/Test - WBS Summary* | EF2F<>NS1.2 (P1-4) [EF<>JXSW] | Not Started | 07/13/26 | 07/24/26 | 12.5 | 12.5 |
|
36.2 |
RPL10.WP4.016000 |
RPL10.Conn NS1.CFD6.48<>03-05 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] | Install (A-End/Passive) Duplex Jumper [RSW<>FSW] | Not Started | 07/13/26 | 07/14/26 | 2.5 | 2.5 |
|
131.2 |
RPL10.WP4.028760 |
RPL10.Conn NS2.CFD5.48<>36-40 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/13/26 | 07/15/26 | 3.8 | 3.8 |
|
131.2 |
RPL10.WP4.028880 |
RPL10.Conn NS2.CFD4.48<>16-20 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/13/26 | 07/16/26 | 5.0 | 5.0 |
|
112.5 |
RPL10.WP4.NS2.01420 |
RPL10.Conn NS2.CFD6 Network - WBS Summary | Network | Not Started | 07/13/26 | 10/08/26 | 78.8 | 78.8 |
|
8.8 |
RPL10.WP4.NS2.01440 |
RPL10.Conn NS2.CFD6 Network Suite [JXSW<>MA] Trunks | Pre ORv3 Rack | Not Started | 07/13/26 | 07/15/26 | 3.8 | 3.8 |
|
60.0 |
GCD.RPL10.4625 |
L3/L4 Start - NS2 Rows 41-48 | NS | Not Started | 07/14/26 | 07/14/26 | 0.0 | 0.0 |
|
150.0 |
GCD.RPL10.4645 |
L3/L4 Start - NS2 Rows 33-40 | NS | Not Started | 07/14/26 | 07/14/26 | 0.0 | 0.0 |
|
150.0 |
GCD.RPL10.6165 |
L3/L4 Start EY - NS1 | EY | Not Started | 07/14/26 | 07/14/26 | 0.0 | 0.0 |
|
138.8 |
ICM.B10.2510.2 |
[NWB] L3/4 Start - NWS2 | Commissioning | Not Started | 07/14/26 | 07/14/26 | 0.0 | 0.0 |
|
150.0 |
RPL.GF.D.N0170.XG |
Infrastructure Complete EF1B | Give Milestones (XREFs) | Not Started | 07/14/26 | 07/14/26 | 0.0 | 0.0 |
|
1910.0 |
RPL10.CTRC.BB.1480 |
RPL10.Int.Build Back.Center-Corr - LO #6,8 - Final Punch Walk | Build Back Interior Leave Out Wall #6 #8 (Center Corr) | Not Started | 07/14/26 | 07/16/26 | 3.8 | 3.8 |
|
145.0 |
RPL10.CX.NS1.01040 |
RPL10.CX.NS1 - L3/L4 - MV Skids (7) Loop 1 | NS1 ELECTRICAL | Not Started | 07/14/26 | 07/22/26 | 8.8 | 8.8 |
|
23.8 |
RPL10.CX.NS2.01030 |
RPL10.CX.NS2 - L3/L4 - House Power (for electrical) | NS2 HOUSE POWER | Not Started | 07/14/26 | 07/27/26 | 12.5 | 12.5 |
|
1.2 |
RPL10.INT.NS2.01500 |
RPL10.Interior.NS2 - Control Fault Domain 4 SQ3.2 - Install Mechanical Side Aisle Cable Tray | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/14/26 | 08/10/26 | 25.0 | 25.0 |
|
18.8 |
RPL10.INT.NS2.01530 |
RPL10.Interior.NS2 - Control Fault Domain 4 SQ3.2 - Install copper from GS.IDF to BMS and EPMS panels (UG from Center ID | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/14/26 | 08/10/26 | 25.0 | 25.0 |
|
-1.2 |
RPL10.SKN.NS12.01060 |
RPL10.SKIN.NS12 - Install Security | Glazing, Doors and Ext Devices | Not Started | 07/14/26 | 07/15/26 | 2.5 | 2.5 |
|
125.0 |
RPL10.W3B.FE.012086 |
RPL10.Conn EF2B<>NS1.CFD5 (P1-4) Install Fiber Trunk (384F) [EF<>SSW] | EF2B<>NS1.2 (P1-4) [EF<>SSW] | Not Started | 07/14/26 | 07/15/26 | 2.5 | 2.5 |
|
21.2 |
RPL10.W3B.FE.012681 |
RPL10.Conn EF2B<>NS1.CFD5 (P1-4) Test Fiber Trunk (288F) [EF<>JXSW] | EF2B<>NS1.2 (P1-4) [EF<>JXSW] | Not Started | 07/14/26 | 07/15/26 | 2.5 | 2.5 |
|
40.0 |
RPL10.W3B.FE.013191 |
RPL10.Conn EF1F<>NS2.CFD6 (P2-3) Test Fiber Trunk (384F) [EF<>SSW] | EF1F<>NS2.1 (P2-3) [EF<>SSW] | Not Started | 07/14/26 | 07/15/26 | 2.5 | 2.5 |
|
48.8 |
RPL10.WP4.01360 |
RPL10.Conn NS1.CFD5.16 Pull Duplex Jumper (LC<>LC) [MA<>JXSW] | Pull Duplex Jumper [MA<>JXSW] | Not Started | 07/14/26 | 07/16/26 | 3.8 | 3.8 |
|
143.8 |
RPL10.CX.NS1.01100 |
RPL10.CX.NS1 - L3/L4 - Control Fault Domain 6 | NS1 Control Fault Domain 6 | Not Started | 07/15/26 | 08/18/26 | 31.2 | 31.2 |
|
30.0 |
RPL10.CX.NS1.01340 |
RPL10.CX.NS1 - L3/L4 - Control Fault Domain 5 - TW Flush and Fill | NS1 Control Fault Domain 5 | Not Started | 07/15/26 | 07/24/26 | 10.0 | 10.0 |
|
30.0 |
RPL10.EY.EF1.01390 |
RPL10.EY.EF1 - Install EY Paving | Hardscape and Landscape | Not Started | 07/15/26 | 07/21/26 | 6.2 | 6.2 |
|
402.5 |
RPL10.EY.EF1.01430 |
RPL10.EY.EF1 - Install RPL-1 FSP Interior Electrical Rough and Lighting | Fiber Support Platform - RPL-1 | Not Started | 07/15/26 | 07/24/26 | 10.0 | 10.0 |
|
227.5 |
RPL10.EY.EF2.01440 |
RPL10.EY.EF2 - Install Early EY Paving | Hardscape and Landscape | Not Started | 07/15/26 | 07/21/26 | 6.2 | 6.2 |
|
396.2 |
RPL10.INT.EF2.01590 |
RPL10.Interior.EF2 - Final Punch Walk | Tie-Ins | Not Started | 07/15/26 | 07/16/26 | 2.5 | 2.5 |
|
168.8 |
RPL10.INT.ENDC.1760 |
RPL10.Interior.End-Corridor - BoW - Install Flooring Tiles/Resinous Flooring in specific rooms | Balance of Walls & Overhead | Not Started | 07/15/26 | 07/24/26 | 10.0 | 10.0 |
|
148.8 |
RPL10.SKN.EF12.01050 |
RPL10.SKIN.EF12 - Install Lighting | Glazing, Doors and Ext Devices | Not Started | 07/15/26 | 07/20/26 | 5.0 | 5.0 |
|
235.0 |
RPL10.SKN.NS43.01040 |
RPL10.SKIN.NS43 - Install Louvers | Glazing, Doors and Ext Devices | Not Started | 07/15/26 | 07/21/26 | 6.2 | 6.2 |
|
228.8 |
RPL10.SKN.NS43.01100 |
RPL10.SKIN.NS43 - Install Scupper and Downspouts | Glazing, Doors and Ext Devices | Not Started | 07/15/26 | 07/21/26 | 6.2 | 6.2 |
|
238.8 |
RPL10.W3B.FE.011566 |
RPL10.Conn EF1F<>NS1.CFD5 (P2-3) Pull Fiber Trunk (384F) [EF<>SSW] | EF1F<>NS1.2 (P2-3) [EF<>SSW] | Not Started | 07/15/26 | 07/16/26 | 2.5 | 2.5 |
|
36.2 |
RPL10.WP3A.EF.07040 |
RPL10.Conn EF2B Infrasturcture 2 (Tier1 & waterfalls etc.) | Infrastructure & Cabling | Not Started | 07/15/26 | 08/11/26 | 25.0 | 25.0 |
|
135.0 |
RPL10.WP3B.FE.01170 |
RPL10.Conn EF1F<>NS1.CFD5 (P2-3) Pull/Install/Test - WBS Summary* | EF1F<>NS1.2 (P2-3) [EF<>SSW] | Not Started | 07/15/26 | 08/11/26 | 25.0 | 25.0 |
|
33.8 |
RPL10.WP4.016020 |
RPL10.Conn NS1.CFD6.48<>06-10 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] | Install (A-End/Passive) Duplex Jumper [RSW<>FSW] | Not Started | 07/15/26 | 07/16/26 | 2.5 | 2.5 |
|
131.2 |
RPL10.WP4.027780 |
RPL10.Conn NS1.CFD4.48<>41-44 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/15/26 | 07/16/26 | 2.5 | 2.5 |
|
121.2 |
RPL10.WP4.028060 |
RPL10.Conn NS1.CFD2.48<>11-15 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/15/26 | 07/21/26 | 6.2 | 6.2 |
|
92.5 |
RPL10.WP4.NS1.01300 |
RPL10.Conn NS1.CFD5 Network Suite [JXSW<>MA] Multi Drop Cable | Pre ORv3 Rack | Not Started | 07/15/26 | 07/24/26 | 10.0 | 10.0 |
|
48.8 |
GCD.RPL10.6265 |
L3/L4 Start EF2 - RPL10 | EF2 | Not Started | 07/16/26 | 07/16/26 | 0.0 | 0.0 |
|
438.8 |
RPL10.CX.EF2.01000 |
RPL10.CX.EF2 - L3, L4, IST - WBS Summary | EF2 | Not Started | 07/16/26 | 09/24/26 | 62.5 | 62.5 |
|
107.5 |
RPL10.CX.EF2.01010 |
RPL10.CX.EF2 - L3 | EF2 | Not Started | 07/16/26 | 08/26/26 | 37.5 | 37.5 |
|
107.5 |
RPL10.CX.EF2.01600 |
RPL10.CX.EF2 - L3/L4 - FW to CRAH Flush and Fill | EF2 | Not Started | 07/16/26 | 08/05/26 | 18.8 | 18.8 |
|
138.8 |
RPL10.EY.NS3.01290 |
RPL10.EY.NS3 - MV Loop 1 - L2 Checklist Completion | Tie-ins | Not Started | 07/16/26 | 07/29/26 | 12.5 | 12.5 |
|
108.8 |
RPL10.EY.NS4.01300 |
RPL10.EY.NS4 - Install Sleeves MEPL | Hardscape and Landscape | Not Started | 07/16/26 | 07/22/26 | 6.2 | 6.2 |
|
237.5 |
RPL10.EY.NS4.01310 |
RPL10.EY.NS4 - MV Loop 2 - L2 Checklist Completion | Tie-ins | Not Started | 07/16/26 | 07/29/26 | 12.5 | 12.5 |
|
165.0 |
RPL10.EY.NS4.01320 |
RPL10.EY.NS4 - Install Hardscape and Landscape - WBS Summary | Hardscape and Landscape | Not Started | 07/16/26 | 01/27/27 | 166.2 | 166.2 |
|
272.5 |
RPL10.INT.NS1.01810 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Pull BMS from panel to devices | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/16/26 | 08/12/26 | 25.0 | 25.0 |
|
21.2 |
RPL10.INT.NS1.01820 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Pull EPMS from panel to devices | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/16/26 | 08/12/26 | 25.0 | 25.0 |
|
21.2 |
RPL10.INT.NS1.01830 |
RPL10.Interior.NS1 - Control Fault Domain 2 SQ5.1 - Set UPS and Panel (2) | Remaining Tie-ins post Mech Side Aisle install | Not Started | 07/16/26 | 08/12/26 | 25.0 | 25.0 |
|
15.0 |
RPL10.INT.SSB.01520 |
RPL10.Interior.SSB - Loading Dock and Storage - Install Shelving | Loading Dock and Storage | Not Started | 07/16/26 | 07/21/26 | 5.0 | 5.0 |
|
146.2 |
RPL10.SKN.NS12.01180 |
RPL10.SKIN.NS12 - QC | Glazing, Doors and Ext Devices | Not Started | 07/16/26 | 07/17/26 | 2.5 | 2.5 |
|
125.0 |
RPL10.W3B.FE.012886 |
RPL10.Conn EF2B<>NS1.CFD5 (P1-4) Test Fiber Trunk (384F) [EF<>SSW] | EF2B<>NS1.2 (P1-4) [EF<>SSW] | Not Started | 07/16/26 | 07/17/26 | 2.5 | 2.5 |
|
40.0 |
RPL10.WP2.GSIDF.2180 |
RPL10.Conn IDF Huts - (GSMDF to GSIDF) NS4 NX03 WBS Summary | GSIDFNX03 | Not Started | 07/16/26 | 08/10/26 | 22.5 | 22.5 |
|
416.2 |
RPL10.WP2.GSIDF.2200 |
RPL10.Conn GSIDFNX03 Set Infrastructure (Racks, Waterfalls etc.) | Infrastructure | Not Started | 07/16/26 | 07/22/26 | 6.2 | 6.2 |
|
157.5 |
RPL10.WP2.GSIDF.2260 |
RPL10.Conn IDF Huts - (GSMDF to GSIDF) NS4 NX04 WBS Summary | GSIDFNX04 | Not Started | 07/16/26 | 08/10/26 | 22.5 | 22.5 |
|
416.2 |
RPL10.WP2.GSIDF.2280 |
RPL10.Conn GSIDFNX04 Set Infrastructure (Racks, Waterfalls etc.) | Infrastructure | Not Started | 07/16/26 | 07/22/26 | 6.2 | 6.2 |
|
157.5 |
RPL10.WP3A.EF1F.1020 |
RPL10.Conn EF1F(OPE)<>EF1F(MBOX) Pull/Install/Test OSP Cabling (for RPL06) - P1 | EF1F<>EF1F | Not Started | 07/16/26 | 07/21/26 | 5.0 | 5.0 |
|
218.8 |
RPL10.WP3A.EF1F.1050 |
RPL10.Conn EF1F(LIU)<>EF2F(MBOX) Pull/Install/Test OSP Cabling (for RPL01) - P3 | EF1F<>EF2F | Not Started | 07/16/26 | 07/27/26 | 10.0 | 10.0 |
|
178.8 |
RPL10.WP4.017860 |
RPL10.Conn NS2.CFD6.48<>03-05 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] | Install (A-End/Passive) Duplex Jumper [RSW<>FSW] | Not Started | 07/16/26 | 07/17/26 | 2.5 | 2.5 |
|
138.8 |
RPL10.WP4.027900 |
RPL10.Conn NS1.CFD3.48<>21-25 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/16/26 | 07/21/26 | 5.0 | 5.0 |
|
102.5 |
RPL10.WP4.028780 |
RPL10.Conn NS2.CFD5.48<>41-44 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/16/26 | 07/17/26 | 2.5 | 2.5 |
|
131.2 |
RPL10.WP4.NS2.01460 |
RPL10.Conn NS2.CFD6 Network Suite [JXSW<>MA] Multi Drop Cable | Pre ORv3 Rack | Not Started | 07/16/26 | 07/20/26 | 3.8 | 3.8 |
|
60.0 |
GCD.RPL10.3529 |
[RPL10] TC Ready: Production Cabling Pathways Complete [NS1 Rows 17-24] | TC Ready: Production Cabling - NS1 | Not Started | 07/17/26 | 07/17/26 | 0.0 | 0.0 |
|
30.0 |
RPL.GF.D.G4640.XG |
Rack & Cabinets Complete - DHD - RPL6 | Give Milestones (XREFs) | Not Started | 07/17/26 | 07/17/26 | 0.0 | 0.0 |
|
182.0 |
RPL10.CX.MCUP.01020 |
RPL10.CX.mCup Loop 2 - L3, L4, IST - WBS Summary | mCup Loop 2 (mCup #2,#4,#6,#8) | Not Started | 07/17/26 | 09/29/26 | 65.0 | 65.0 |
|
372.5 |
RPL10.CX.MCUP.01370 |
RPL10.CX.mCup Loop 2 - L3/L4 - mCUP - Flush and Fill - mCup Yard - Loop 2 (Phase 3) | Fill and Flush | Not Started | 07/17/26 | 07/23/26 | 6.2 | 6.2 |
|
120.0 |
RPL10.INT.ENDC.01320 |
RPL10.Interior.End-Corridor - BoW - Install Toilet Accessories | Balance of Walls & Overhead | Not Started | 07/17/26 | 07/27/26 | 8.8 | 8.8 |
|
172.5 |
RPL10.WP4.016040 |
RPL10.Conn NS1.CFD6.48<>11-15 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] | Install (A-End/Passive) Duplex Jumper [RSW<>FSW] | Not Started | 07/17/26 | 07/20/26 | 2.5 | 2.5 |
|
131.2 |
RPL10.WP4.027800 |
RPL10.Conn NS1.CFD4.48<>46-49 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/17/26 | 07/17/26 | 1.2 | 1.2 |
|
121.2 |
RPL10.WP4.028900 |
RPL10.Conn NS2.CFD4.48<>21-25 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] | Prefab | Not Started | 07/17/26 | 07/22/26 | 5.0 | 5.0 |
|
112.5 |
GCD.RPL10.4105 |
[RPL10] TC Ready: Production Cabling Pathways Complete [NS2 Rows 9-16] | TC Ready: Production Cabling - NS2 | Not Started | 07/20/26 | 07/20/26 | 0.0 | 0.0 |
|
15.0 |