Schedule Viewer

Last schedule upload: D3-R25005-00-RPL06 — 6139 activities — 04/16/2026 08:19 AM CT
RPL10 - GC LIVE SCHEDULE - Data Date 20260412.xer · Uploaded Apr 16, 2026 12:51 PM · 8408 activities
Experimental Auto-populate checklist dates from schedule:
Clear
100
Activities Shown
0
Completed
0
In Progress
5
Critical
Activity ID Activity Name WBS Status Start Finish Dur (d) Rem (d) % Comp Float (d)
RPL10.WP4.019440 RPL10.Conn NS2.CFD2.48<>36-40 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/21/26 12/22/26 2.5 2.5
0%
21.2
RPL10.WP4.019560 RPL10.Conn NS2.CFD1.48<>16-20 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/21/26 12/22/26 2.5 2.5
0%
11.2
RPL10.WP4.019860 RPL10.Conn NS3.CFD1.48<>41-44 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/21/26 12/22/26 2.5 2.5
0%
138.8
RPL10.WP4.025280 RPL10.Conn NS2.CFD1.48<>47 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/21/26 12/21/26 1.2 1.2
0%
27.5
RPL10.WP4.025300 RPL10.Conn NS3.CFD1.01<>01 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/21/26 12/21/26 1.2 1.2
0%
133.8
RPL10.WP4.026380 RPL10.Conn NS4.CFD1.07<>07 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/21/26 12/21/26 1.2 1.2
0%
128.8
RPL10.WP4.031780 RPL10.Conn NS3.CFD5.48<>41-44 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] Prefab Not Started 12/21/26 12/22/26 2.5 2.5
0%
111.2
RPL10.WP4.033280 RPL10.Conn NS2.CFD2.40 Install (Z-End/Active) Duplex Jumper (LC<>LC) [MA<>JXSW] Install Duplex Jumper [MA<>JXSW] Not Started 12/21/26 12/22/26 2.5 2.5
0%
26.2
RPL10.WP4.034740 RPL10.Conn NS1.CFD1 Pull/Install In-Rack Fanout (MPO<>MMC) [EB<>DR] [EB<>DR] Not Started 12/21/26 12/22/26 2.5 2.5
0%
0.0
RPL10.WP4.05980 RPL10.Conn NS3.CFD4.48<>46-49 Pull Duplex Jumper (LC<>LC) [RSW<>FSW] Pull Duplex Jumper [RSW<>FSW] Not Started 12/21/26 12/21/26 1.2 1.2
0%
135.0
RPL10.WP4.08180 RPL10.Conn NS4.CFD5.48<>46-49 Pull Duplex Jumper (LC<>LC) [RSW<>FSW] Pull Duplex Jumper [RSW<>FSW] Not Started 12/21/26 12/21/26 1.2 1.2
0%
127.5
RPL10.WP4.08380 RPL10.Conn NS4.CFD6.48<>46-49 Pull Duplex Jumper (LC<>LC) [RSW<>FSW] Pull Duplex Jumper [RSW<>FSW] Not Started 12/21/26 12/21/26 1.2 1.2
0%
127.5
RPL10.WP4.NS3.01380 RPL10.Conn NS3.CFD1 Network Suite [JXSW<>MA] Fanouts Post ORv3 Rack Not Started 12/21/26 12/23/26 3.8 3.8
0%
48.8
RPL10.WP4.NS4.01260 RPL10.Conn NS4.CFD1 Network Suite Management and Console In - Row Cabling - PON Post ORv3 Rack Not Started 12/21/26 12/23/26 3.8 3.8
0%
43.8
RPL10.CX.NS3.01110 RPL10.CX.NS3 - L3/L4 - Control Fault Domain 2 NS3 Control Fault Domain 2 Not Started 12/22/26 01/14/27 20.0 20.0
0%
36.2
RPL10.CX.NS3.01400 RPL10.CX.NS3 - L3/L4 - Control Fault Domain 3 - TW Flush and Fill NS3 Control Fault Domain 3 Not Started 12/22/26 01/04/27 10.0 10.0
0%
43.8
RPL10.ENDC.BB.1060 RPL10.Ext.Build Back.End-Corr - LO #3 - Install Exterior Backing, In Wall Build Back Exterior Leave Out Wall #3 (Tent Area) Not Started 12/22/26 12/28/26 5.0 5.0
0%
72.5
RPL10.EY.NS3.01360 RPL10.EY.NS3 - Demo of Tent Tent and Temp Conditions Not Started 12/22/26 01/06/27 12.5 12.5
0%
67.5
RPL10.W3B.FE.011046 RPL10.Conn EF1B<>NS3.CFD3 (P2-3) Pull Fiber Trunk (288F) [EF<>JXSW] EF1B<>NS3.3 (P2-3) [EF<>JXSW] Not Started 12/22/26 12/29/26 6.2 6.2
0%
42.5
RPL10.W3B.FE.012426 RPL10.Conn EF1F<>NS3.CFD2 (P2-3) Install Fiber Trunk (384F) [EF<>SSW] EF1F<>NS3.2 (P2-3) [EF<>SSW] Not Started 12/22/26 12/23/26 2.5 2.5
0%
37.5
RPL10.W3B.FE.013041 RPL10.Conn EF1F<>NS3.CFD2 (P2-3) Test Fiber Trunk (288F) [EF<>JXSW] EF1F<>NS3.2 (P2-3) [EF<>JXSW] Not Started 12/22/26 12/23/26 2.5 2.5
0%
52.5
RPL10.WP3B.FE.08440 RPL10.Conn EF1B<>NS3.CFD3 (P2-3) Pull/Install/Test - WBS Summary EF1B<>NS3.3 (P2-3) [EF<>JXSW] Not Started 12/22/26 01/15/27 21.2 21.2
0%
48.8
RPL10.WP4.010280 RPL10.Conn NS4.CFD2 Pull/Install Trunk (384F) [RSW<>FSW] Pull/Install Trunk & Multidrop Cable Not Started 12/22/26 12/31/26 8.8 8.8
0%
113.8
RPL10.WP4.021880 RPL10.Conn NS4.CFD2.16 Install (A-End/Passive) Duplex Jumper (LC<>LC) [MA<>JXSW] Install (A-End/Passive) Duplex Jumper [MA<>JXSW] Not Started 12/22/26 12/23/26 2.5 2.5
0%
127.5
RPL10.WP4.022040 RPL10.Conn NS4.CFD2.48<>36-40 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/22/26 12/23/26 2.5 2.5
0%
122.5
RPL10.WP4.025320 RPL10.Conn NS3.CFD1.02<>01 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/22/26 12/22/26 1.2 1.2
0%
133.8
RPL10.WP4.026400 RPL10.Conn NS4.CFD1.08<>07 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/22/26 12/22/26 1.2 1.2
0%
128.8
RPL10.WP4.026420 RPL10.Conn NS4.CFD2.09<>09 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/22/26 12/22/26 1.2 1.2
0%
120.0
RPL10.WP4.031900 RPL10.Conn NS3.CFD6.48<>21-25 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] Prefab Not Started 12/22/26 12/28/26 5.0 5.0
0%
92.5
RPL10.WP4.033300 RPL10.Conn NS4.CFD2.09 Install (Z-End/Active) Duplex Jumper (LC<>LC) [MA<>JXSW] Install Duplex Jumper [MA<>JXSW] Not Started 12/22/26 12/23/26 2.5 2.5
0%
110.0
RPL10.WP4.034640 RPL10.Conn NS2.CFD1 Pull/Install Trunk (96F) [BB<>EB] [BB<>EB] Not Started 12/22/26 12/23/26 2.5 2.5
0%
-43.8
RPL10.WP4.05400 RPL10.Conn NS3.CFD3.23 Pull Duplex Jumper (LC<>LC) [MA<>JXSW] Pull Duplex Jumper [MA<>JXSW] Not Started 12/22/26 12/24/26 3.8 3.8
0%
127.5
RPL10.WP4.07880 RPL10.Conn NS4.CFD5.35 Pull Duplex Jumper (LC<>LC) [MA<>JXSW] Pull Duplex Jumper [MA<>JXSW] Not Started 12/22/26 12/24/26 3.8 3.8
0%
100.0
RPL10.WP4.09480 RPL10.Conn NS4.CFD1 Pull/Install Trunk (192F) [FSW<>SSW] Pull/Install Trunk Not Started 12/22/26 01/04/27 10.0 10.0
0%
120.0
RPL10.WP4.09500 RPL10.Conn NS4.CFD2 Pull/Install Trunk (192F) [FSW<>SSW] Pull/Install Trunk & Multidrop Cable Not Started 12/22/26 12/30/26 7.5 7.5
0%
122.5
RPL10.WP4.NS3.02760 RPL10.Conn NS3.CFD2 - Install ORv3 OFE - Passive In-row Racks, Racks (ORv3Ns, MCRs) & PON Not Started 12/22/26 12/31/26 8.8 8.8
0%
38.8
RPL10.WP4.NS3.02780 RPL10.Conn NS3.CFD2 - Deliver & Assemble - PON OFE - Passive In-row Racks, Racks (ORv3Ns, MCRs) & PON Not Started 12/22/26 12/31/26 8.8 8.8
0%
58.8
RPL10.WP4.NS4.01400 RPL10.Conn NS4.CFD2 Network Suite [JXSW<>MA] Fanouts Post ORv3 Rack Not Started 12/22/26 01/04/27 10.0 10.0
0%
35.0
RPL10.WP4.NS4.02840 RPL10.Conn NS4.CFD3 - Install ORv3 OFE - Passive In-row Racks, Racks (ORv3Ns, MCRs) & PON Not Started 12/22/26 12/31/26 8.8 8.8
0%
41.2
RPL10.WP4.NS4.02860 RPL10.Conn NS4.CFD3 - Deliver & Assemble - PON OFE - Passive In-row Racks, Racks (ORv3Ns, MCRs) & PON Not Started 12/22/26 12/31/26 8.8 8.8
0%
61.2
GCD.RPL10.6085 [RPL10] TC Ready: Production Cabling Pathways Complete [NS3 Rows 33-40] TC Ready: Production Cabling - NS3 Not Started 12/23/26 12/23/26 0.0 0.0
0%
81.2
RPL10.EY.NS4.01410 RPL10.EY.NS4 - Install Remaining CU (2) Build Back Exterior Leave Out Wall #4 (Tent Area) Not Started 12/23/26 12/28/26 2.5 2.5
0%
83.8
RPL10.W3B.FE.011271 RPL10.Conn EF1B<>NS4.CFD5 (P2-3) Pull Fiber Trunk (384F) [EF<>SSW] EF1B<>NS4.5 (P2-3) [EF<>SSW] Not Started 12/23/26 12/24/26 2.5 2.5
0%
77.5
RPL10.W3B.FE.011531 RPL10.Conn EF2F<>NS3.CFD4 (P1-4) Pull Fiber Trunk (288F) [EF<>JXSW] EF2F<>NS3.4 (P1-4) [EF<>JXSW] Not Started 12/23/26 12/28/26 3.8 3.8
0%
66.2
RPL10.WP3B.FE.08500 RPL10.Conn EF2F<>NS3.CFD4 (P1-4) Pull/Install/Test - WBS Summary* EF2F<>NS3.4 (P1-4) [EF<>JXSW] Not Started 12/23/26 02/08/27 38.8 38.8
0%
45.0
RPL10.WP3B.FE.09520 RPL10.Conn EF1B<>NS4.CFD5 (P2-3) Pull/Install/Test - WBS Summary* EF1B<>NS4.5 (P2-3) [EF<>SSW] Not Started 12/23/26 02/22/27 50.0 50.0
0%
38.8
RPL10.WP4.015820 RPL10.Conn NS4.CFD6.41<>41 Pull & Install Simplex Jumper at A- End (SC<>LC) [PON] Pull Simplex Jumper [PON] Not Started 12/23/26 12/28/26 3.8 3.8
0%
110.0
RPL10.WP4.015860 RPL10.Conn NS4.CFD6.43<>43 Pull & Install Simplex Jumper at A- End (SC<>LC) [PON] Pull Simplex Jumper [PON] Not Started 12/23/26 12/28/26 3.8 3.8
0%
110.0
RPL10.WP4.019460 RPL10.Conn NS2.CFD2.48<>41-44 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/23/26 12/24/26 2.5 2.5
0%
21.2
RPL10.WP4.019580 RPL10.Conn NS2.CFD1.48<>21-25 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/23/26 12/24/26 2.5 2.5
0%
11.2
RPL10.WP4.019880 RPL10.Conn NS3.CFD1.48<>46-49 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/23/26 12/24/26 2.5 2.5
0%
138.8
RPL10.WP4.025340 RPL10.Conn NS3.CFD1.03<>03 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/23/26 12/23/26 1.2 1.2
0%
133.8
RPL10.WP4.026440 RPL10.Conn NS4.CFD2.10<>09 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/23/26 12/23/26 1.2 1.2
0%
120.0
RPL10.WP4.031800 RPL10.Conn NS3.CFD5.48<>46-49 Prefab Duplex Jumper (LC<>LC) [RSW<>FSW] Prefab Not Started 12/23/26 12/23/26 1.2 1.2
0%
111.2
RPL10.WP4.034660 RPL10.Conn NS1.CFD1 Pull/Install Ext. Trunk (24F) [DR<>BB] [DR<>BB] Not Started 12/23/26 12/24/26 2.5 2.5
0%
0.0
RPL10.WP4.05700 RPL10.Conn NS3.CFD4.28 Pull Duplex Jumper (LC<>LC) [MA<>JXSW] Pull Duplex Jumper [MA<>JXSW] Not Started 12/23/26 12/28/26 3.8 3.8
0%
115.0
RPL10.WP4.NS2.03180 RPL10.Conn NS2.CFD2 Network Suite Management and Console In - Row Cabling - PON Post ORv3 Rack Not Started 12/23/26 01/05/27 10.0 10.0
0%
6.2
GCD.RPL10.5425 L3/L4 Finish - NS3 Rows 1-8 NS Not Started 12/24/26 12/24/26 0.0 0.0
0%
122.5
RPL10.Conn.MS.01990 RPL10.Conn NS2.CFD2 FIM NS2 Not Started 12/24/26 01/25/27 25.0 25.0
0%
6.2
RPL10.INT.NS3.01950 RPL10.Interior.NS3 - Control Fault Domain 6 SQ12.2 - L2 Checklist Completion Remaining Tie-ins post Mech Side Aisle install Not Started 12/24/26 01/25/27 25.0 25.0
0%
67.5
RPL10.INT.NS3.03100 RPL10.Interior.NS3 - Control Fault Domain 6 SQ12.2 - Install FA Terminations to Fire Alarm Panel (In Riser Room) Remaining Tie-ins post Mech Side Aisle install Not Started 12/24/26 12/31/26 6.2 6.2
0%
86.2
RPL10.INT.NS4.01760 RPL10.Conn NS4.CFD5 - Set Passive Racks for WP3B Infrastructure Not Started 12/24/26 12/29/26 3.8 3.8
0%
63.8
RPL10.INT.NS4.03040 RPL10.Conn NS4.CFD5 - Set Passive Racks for PON Infrastructure Not Started 12/24/26 12/29/26 3.8 3.8
0%
115.0
RPL10.W3B.FE.011926 RPL10.Conn EF2B<>NS3.CFD3 (P1-4) Install Fiber Trunk (288F) [EF<>JXSW] EF2B<>NS3.3 (P1-4) [EF<>JXSW] Not Started 12/24/26 12/29/26 3.8 3.8
0%
37.5
RPL10.W3B.FE.012461 RPL10.Conn EF1F<>NS4.CFD3 (P2-3) Install Fiber Trunk (384F) [EF<>SSW] EF1F<>NS4.3 (P2-3) [EF<>SSW] Not Started 12/24/26 12/28/26 2.5 2.5
0%
37.5
RPL10.W3B.FE.013066 RPL10.Conn EF1F<>NS4.CFD3 (P2-3) Test Fiber Trunk (288F) [EF<>JXSW] EF1F<>NS4.3 (P2-3) [EF<>JXSW] Not Started 12/24/26 12/28/26 2.5 2.5
0%
47.5
RPL10.W3B.FE.013226 RPL10.Conn EF1F<>NS3.CFD2 (P2-3) Test Fiber Trunk (384F) [EF<>SSW] EF1F<>NS3.2 (P2-3) [EF<>SSW] Not Started 12/24/26 12/28/26 2.5 2.5
0%
52.5
RPL10.WA.EF1.01000 RPL10.WA - OFE to AC - EF1 Weather Allowance Not Started 12/24/26 01/02/27 12.5 12.5
0%
33.8
RPL10.WP4.014620 RPL10.Conn NS3.CFD4.29<>29 Pull & Install Simplex Jumper at A- End (SC<>LC) [PON] Pull Simplex Jumper [PON] Not Started 12/24/26 12/28/26 2.5 2.5
0%
130.0
RPL10.WP4.014660 RPL10.Conn NS3.CFD4.31<>31 Pull & Install Simplex Jumper at A- End (SC<>LC) [PON] Pull Simplex Jumper [PON] Not Started 12/24/26 12/28/26 2.5 2.5
0%
132.5
RPL10.WP4.015680 RPL10.Conn NS4.CFD5.34<>33 Pull & Install Simplex Jumper at A- End (SC<>LC) [PON] Pull Simplex Jumper [PON] Not Started 12/24/26 12/29/26 3.8 3.8
0%
112.5
RPL10.WP4.015720 RPL10.Conn NS4.CFD5.36<>35 Pull & Install Simplex Jumper at A- End (SC<>LC) [PON] Pull Simplex Jumper [PON] Not Started 12/24/26 12/29/26 3.8 3.8
0%
112.5
RPL10.WP4.022060 RPL10.Conn NS4.CFD2.48<>41-44 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/24/26 12/28/26 2.5 2.5
0%
122.5
RPL10.WP4.025360 RPL10.Conn NS3.CFD1.04<>03 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/24/26 12/24/26 1.2 1.2
0%
133.8
RPL10.WP4.026460 RPL10.Conn NS4.CFD2.11<>11 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/24/26 12/24/26 1.2 1.2
0%
120.0
RPL10.WP4.033320 RPL10.Conn NS4.CFD2.10 Install (Z-End/Active) Duplex Jumper (LC<>LC) [MA<>JXSW] Install Duplex Jumper [MA<>JXSW] Not Started 12/24/26 12/28/26 2.5 2.5
0%
110.0
RPL10.WP4.06000 RPL10.Conn NS3.CFD5.33 Pull Duplex Jumper (LC<>LC) [MA<>JXSW] Pull Duplex Jumper [MA<>JXSW] Not Started 12/24/26 12/29/26 3.8 3.8
0%
102.5
RPL10.WP4.06160 RPL10.Conn NS3.CFD5.48<>03-05 Pull Duplex Jumper (LC<>LC) [RSW<>FSW] Pull Duplex Jumper [RSW<>FSW] Not Started 12/24/26 12/29/26 3.8 3.8
0%
111.2
RPL10.WP4.06180 RPL10.Conn NS3.CFD5.48<>06-10 Pull Duplex Jumper (LC<>LC) [RSW<>FSW] Pull Duplex Jumper [RSW<>FSW] Not Started 12/24/26 12/29/26 3.8 3.8
0%
112.5
RPL10.WP4.06200 RPL10.Conn NS3.CFD5.48<>11-15 Pull Duplex Jumper (LC<>LC) [RSW<>FSW] Pull Duplex Jumper [RSW<>FSW] Not Started 12/24/26 01/04/27 7.5 7.5
0%
112.5
RPL10.WP4.09860 RPL10.Conn NS2.CFD1.03<>45 Pull/Install Trunk (384F) [MA<>EB] [MA<>EB] Not Started 12/24/26 12/31/26 6.2 6.2
0%
-43.8
RPL10.WP4.NS3.01400 RPL10.Conn NS3.CFD1 GSMDF <> Network Suites Management Trunks Post ORv3 Rack Not Started 12/24/26 12/29/26 3.8 3.8
0%
48.8
RPL10.WP4.NS3.03060 RPL10.Conn NS3.CFD4 Infrastructure - WBS Summary Infrastructure Not Started 12/24/26 12/30/26 5.0 5.0
0%
62.5
RPL10.WP4.NS3.03080 RPL10.Conn NS3.CFD4 Infrastructure Infrastructure Not Started 12/24/26 12/30/26 5.0 5.0
0%
62.5
RPL10.WP4.NS4.01280 RPL10.Conn NS4.CFD1 Network Suite Management and Console In - Rack Fanout - PON Post ORv3 Rack Not Started 12/24/26 12/29/26 3.8 3.8
0%
43.8
RPL10.Conn.MS.01010 Wifi Ready - All locations Connectivity Milestones Not Started 12/28/26 12/28/26 0.0 0.0
0%
297.5
RPL10.Conn.MS.01450 Wifi Ready - NS3 Connectivity Milestones Not Started 12/28/26 12/28/26 0.0 0.0
0%
297.5
RPL10.ENDC.BB.1980 RPL10.Int.Build Back.End-Corr - LO #10 - Final Punch Walk Build Back Interior Leave Out Wall #10 (End Corr) Not Started 12/28/26 12/29/26 2.5 2.5
0%
117.5
RPL10.ENDC.BB.3265 RPL10.Ext.Build Back.End-Corr - LO #4 - MEPF Trim Out Build Back Exterior Leave Out Wall #4 (Tent Area) Not Started 12/28/26 01/11/27 12.5 12.5
0%
92.5
RPL10.EY.NS4.01440 RPL10.EY.NS4 - Install Remaining Mechanical Tie-ins Build Back Exterior Leave Out Wall #4 (Tent Area) Not Started 12/28/26 01/04/27 6.2 6.2
0%
83.8
RPL10.EY.NS4.01450 RPL10.EY.NS4 - Install Remaining Electrical Tie-ins Build Back Exterior Leave Out Wall #4 (Tent Area) Not Started 12/28/26 01/04/27 6.2 6.2
0%
83.8
RPL10.W3B.FE.011391 RPL10.Conn EF2B<>NS4.CFD5 (P1-4) Pull Fiber Trunk (384F) [EF<>SSW] EF2B<>NS4.5 (P1-4) [EF<>SSW] Not Started 12/28/26 12/30/26 3.8 3.8
0%
61.2
RPL10.W3B.FE.011476 RPL10.Conn EF1F<>NS4.CFD5 (P2-3) Pull Fiber Trunk (288F) [EF<>JXSW] EF1F<>NS4.5 (P2-3) [EF<>JXSW] Not Started 12/28/26 12/31/26 5.0 5.0
0%
77.5
RPL10.WP3B.FE.09400 RPL10.Conn EF1F<>NS4.CFD5 (P2-3) Pull/Install/Test - WBS Summary EF1F<>NS4.5 (P2-3) [EF<>JXSW] Not Started 12/28/26 02/25/27 51.2 51.2
0%
37.5
RPL10.WP3B.FE.09500 RPL10.Conn EF2B<>NS4.CFD5 (P1-4) Pull/Install/Test - WBS Summary EF2B<>NS4.5 (P1-4) [EF<>SSW] Not Started 12/28/26 02/05/27 35.0 35.0
0%
41.2
RPL10.WP4.019480 RPL10.Conn NS2.CFD2.48<>46-49 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/28/26 12/29/26 2.5 2.5
0%
21.2
RPL10.WP4.019600 RPL10.Conn NS2.CFD1.48<>26-30 Install (A-End/Passive) Duplex Jumper (LC<>LC) [RSW<>FSW] Install (A-End/Passive) Duplex Jumper [RSW<>FSW] Not Started 12/28/26 12/29/26 2.5 2.5
0%
11.2
RPL10.WP4.025380 RPL10.Conn NS3.CFD1.05<>05 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/28/26 12/28/26 1.2 1.2
0%
133.8
RPL10.WP4.026480 RPL10.Conn NS4.CFD2.12<>11 Install Simplex Jumper at Z- End (SC<>LC) [PON] Install Simplex Jumper [PON] Not Started 12/28/26 12/28/26 1.2 1.2
0%
120.0
RPL10.WP4.034680 RPL10.Conn NS1.CFD1 Pull Duplex Jumper (LC<>LC) [DR<>BB] [DR<>BB] Not Started 12/28/26 12/28/26 1.2 1.2
0%
0.0