| Activity ID | Activity Name | WBS | Status | Start | Finish | Dur (d) | Rem (d) | % Comp | Float (d) |
|---|---|---|---|---|---|---|---|---|---|
RPL10.FEN.NS3.1430 |
EF1-W Row 3,5 <>FEN NS3 Odd Row #: Path3 - 432f JXSW<>SSW Trunks Permlink Testing [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 16.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS3.1440 |
EF2-W Row 3,5 <>FEN NS3 Even Row #: Path4 - 432f JXSW<>SSW Trunks Permlink Testing [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 16.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS3.1450 |
FEN NS3: PON Management In-Row Cable Pull | PON Management | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS3.1460 |
FEN NS3: PON Management In-Row Cable Install | PON Management | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1000 |
EF1-E Row 3,5 <>FEN NS4 Odd Row #: Path1 - 432f JXSW<>SSW Trunks Pull [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1010 |
EF2-E Row 3,5 <>FEN NS4 Even Row #: Path2 - 432f JXSW<>SSW Trunks Pull [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1020 |
EF1-W Row 3,5 <>FEN NS4 Odd Row #: Path3 - 432f JXSW<>SSW Trunks Pull [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1030 |
EF2-W Row 3,5 <>FEN NS4 Even Row #: Path4 - 432f JXSW<>SSW Trunks Pull [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1040 |
FEN NS4: SSW<>XSW 8MMC24P<>8MMC24R Ext Trunks Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 17.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1050 |
FEN NS1: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Pull [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1060 |
FEN NS2: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Pull [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1070 |
FEN NS3: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Pull [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1080 |
FEN NS4: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Pull [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1090 |
FEN NS4: 384f End Row IDF<>IDF SSW<>FSW Trunks Pull [Tier 3] | End Row IDF<>IDF Trunk | Complete | 10/17/24 | 10/17/24 | 1.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1100 |
FEN NS4: FSW<>SSW 8MMC24P<>8MMC24P In-Row Ext Trunks Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 3.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1110 |
FEN NS4: FSW<>SSW 8MMC24P<>8MMC24R Across Cold-Aisle Ext Trunks Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1120 |
FEN NS4: FSW<>SSW 16MMC24P<>16MMC24R Across Cold-Aisle Ext Trunks Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 2.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1130 |
FEN NS4: 384f End Row IDF<>IDF FSW<>RSW Trunks Pull [Tier 3] | End Row IDF<>IDF Trunk | Complete | 10/17/24 | 10/17/24 | 1.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1140 |
FEN NS4: RSW<>FSW 1MMC16P<>LC/DX Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 3.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1150 |
FEN NS4: RSW<>FSW 12MMC24P<>LC/DX Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 17.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1160 |
FEN NS4: RSW<>FSW 12MMC24P<>12MMC24R Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1170 |
FEN NS4: RSW<>FSW 2MMC24P<>2MMC24R Pull [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1180 |
FEN NS4: Install ORV3N | Infrastructure | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1190 |
FEN NS4: Install Waterfall | Infrastructure | Complete | 10/17/24 | 10/17/24 | 12.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1200 |
FEN NS4: Install Rack Power Distribution Units (PDU) | Infrastructure | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1210 |
FEN NS4: Install End Row PDUs | Infrastructure | Complete | 10/17/24 | 10/17/24 | 3.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1220 |
FEN NS4: Rack & Stack Management & Console | Rack & Stack | Complete | 10/17/24 | 10/17/24 | 2.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1230 |
FEN NS1: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Install [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1240 |
FEN NS2: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Install [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1250 |
FEN NS3: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Install [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1260 |
FEN NS4: Row3-6 SSW<>JXSW 8MMC24R<>24MMC8P Install [Tier 2] | Network Suite [SSW<>JXSW] Multi Drop Cable | Complete | 10/17/24 | 10/17/24 | 10.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1270 |
EF1-E Row 3,5 <>FEN NS4 Odd Row #: Path1 - 432f JXSW<>SSW Trunks Install [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1280 |
EF2-E Row 3,5 <>FEN NS4 Even Row #: Path2 - 432f JXSW<>SSW Trunks Install [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1290 |
EF2-W Row 3,5 <>FEN NS4 Odd Row #: Path3 - 432f JXSW<>SSW Trunks Install [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1300 |
EF2-W Row 3,5 <>FEN NS4 Even Row #: Path4 - 432f JXSW<>SSW Trunks Install [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 8.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1310 |
FEN NS4: SSW<>XSW 8MMC24P<>8MMC24R Ext Trunks Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 27.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1320 |
FEN NS4: FSW<>SSW 8MMC24P<>8MMC24P In-Row Ext Trunks Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1330 |
FEN NS4: FSW<>SSW 8MMC24P<>8MMC24R Across Cold-Aisle Ext Trunks Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1340 |
FEN NS4: FSW<>SSW 16MMC24P<>16MMC24R Across Cold-Aisle Ext Trunks Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1350 |
FEN NS4: RSW<>FSW 1MMC16P<>LC/DX Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 3.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1360 |
FEN NS4: RSW<>FSW 12MMC24P<>LC/DX Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1370 |
FEN NS4: RSW<>FSW 12MMC24P<>12MMC24R Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1380 |
FEN NS4: RSW<>FSW 2MMC24P<>2MMC24R Install [Tier 2.2] | Megapod In-Row/across Cold Aisle Cabling | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1390 |
FEN NS4: 384f End Row IDF<>IDF SSW<>FSW Trunks Install [Tier 3] | End Row IDF<>IDF Trunk | Complete | 10/17/24 | 10/17/24 | 1.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1400 |
FEN NS4: 384f End Row IDF<>IDF FSW<>RSW Trunks Install [Tier 3] | End Row IDF<>IDF Trunk | Complete | 10/17/24 | 10/17/24 | 1.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1410 |
EF1-E Row 3,5 <>FEN NS4 Odd Row #: Path1 - 432f JXSW<>SSW Trunks Permlink Testing [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1420 |
EF2-E Row 3,5 <>FEN NS4 Even Row #: Path2 - 432f JXSW<>SSW Trunks Permlink Testing [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1430 |
EF1-W Row 3,5 <>FEN NS4 Odd Row #: Path3 - 432f JXSW<>SSW Trunks Permlink Testing [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1440 |
EF2-W Row 3,5 <>FEN NS4 Even Row #: Path4 - 432f JXSW<>SSW Trunks Permlink Testing [Tier 4] | NS<>DH JXSW<>SSW Trunks | Complete | 10/17/24 | 10/17/24 | 16.2 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1450 |
FEN NS4: PON Management In-Row Cable Pull | PON Management | Complete | 10/17/24 | 10/17/24 | 3.8 | 0.0 |
|
0.0 |
RPL10.FEN.NS4.1460 |
FEN NS4: PON Management In-Row Cable Install | PON Management | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.01080 |
RPL10.Interior.Center-Corridor - Priority Walls - Electrical OBSOLETE | Obsolete | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.01110 |
RPL10.Interior.Center-Corridor - Priority Walls - Controls / EPMS / BMS OBSOLETE | Obsolete | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.01160 |
RPL10.Interior.Center-Corridor - Spoke Parts, Tech, SCR, lnverter Room, UPS Gallery, Bathrooms, etc.) - OBSOLETE | Obsolete | Active | 10/17/24 | 07/27/32 | 2448.8 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.01450 |
RPL10.Interior.Center-Corridor - BoW - Install DAS ***OBSOLETE*** | Obsolete | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.01570 |
RPL10.Interior.Center-Corridor - Priority Walls - Install Plumbing OBSOLETE | Obsolete | Complete | 10/17/24 | 10/17/24 | 12.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.01950 |
RPL10.Interior.Center-Corridor - Priority - Install Drywall at Exterior Walls (Highside OH space) OBSOLETE | Obsolete | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05420 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Frame Pony Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05440 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - MEP OH Pentrations OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05460 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Hang Drywall Pony Wall (both sides)OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05480 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Tape Float Paint Pony Wall (both sides) OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 12.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05500 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Remaining Hangers & Strut (All Trades) OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05520 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Frame Remaining Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05540 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Mechanical Inwall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05560 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Electrical Inwall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05580 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Fire Alarm/ BMS inwall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05600 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Backing Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05620 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - One Side Drywall Remaining Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05640 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Tape Float Paint One Side Remaining Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05660 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Two Side Drywall Remaining Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05680 |
RPL10.Interior.CTRC - Priority - Grid line 10-25 - P3 - Tape Float Paint Two Side Remaining Wall OBSOLETE | Priority Wall (P3) - Grid Line 10-25 | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05700 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Frame Pony Wall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05720 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - MEP OH Pentrations OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05740 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Frame Remaining Wall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05760 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Hang Drywall Pony Wall (both sides) OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05780 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Tape Float Paint Pony Wall (both sides) OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 12.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05800 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - One Side Drywall Remaining Wall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05820 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Backing Wall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05840 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Mechanical Inwall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05860 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Electrical Inwall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05880 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Tape Float Paint One Side Remaining Wall ***** OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05900 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Two Side Drywall Remaining Wall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05920 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Tape Float Paint Two Side Remaining Wall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05940 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Remaining Hangers & Strut (All Trades) OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05960 |
RPL10.Interior.CTRC - Priority - Grid line 10-16 - P4 - Fire Alarm/ BMS inwall OBSOLETE | Priority Wall (P4) - Grid Line 10-D | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.05980 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Frame Pony Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06000 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - MEP OH Pentrations OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06020 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Frame Remaining Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06040 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Hang Drywall Pony Wall (both sides) OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06060 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Tape Float Paint Pony Wall (both sides) OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 12.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06080 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - One Side Drywall Remaining Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06100 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Backing Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06120 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Mechanical Inwall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06140 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Electrical Inwall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06160 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Tape Float Paint One Side Remaining Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06180 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Two Side Drywall Remaining Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 7.5 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06200 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Tape Float Paint Two Side Remaining Wall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 15.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06220 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Remaining Hangers & Strut (All Trades) OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06240 |
RPL10.Interior.CTRC - Priority - Grid line EF1 - P6 - Fire Alarm/ BMS inwall OBSOLETE | Priority Wall (P6) - EF1 Walls | Complete | 10/17/24 | 10/17/24 | 5.0 | 0.0 |
|
0.0 |
RPL10.INT.CTRC.06260 |
RPL10.Interior.CTRC - Priority - Grid line EF2 - P6 - Frame Pony Wall OBSOLETE | Priority Wall (P6) - EF2 Walls | Complete | 10/17/24 | 10/17/24 | 6.2 | 0.0 |
|
0.0 |