Last schedule upload: D3-R25005-00-RPL06 — 6139 activities — 04/16/2026 08:19 AM CT
RPL09 - GC LIVE SCHEDULE - Data Date 2026.04.12.xer
· Uploaded Apr 16, 2026 01:12 PM
· 5201 activities
Experimental
Auto-populate checklist dates from schedule:
100
Activities Shown
0
Completed
0
In Progress
5
Critical
| Activity ID | Activity Name | WBS | Status | Start | Finish | Dur (d) | Rem (d) | % Comp | Float (d) |
|---|---|---|---|---|---|---|---|---|---|
RPL09.WP4.034620 |
RPL09.Conn DHD.29.04 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/25/27 | 11/05/27 | 12.5 | 12.5 |
|
221.2 |
RPL09.WP4.034640 |
RPL09.Conn DHD.30.08 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/25/27 | 11/05/27 | 12.5 | 12.5 |
|
221.2 |
RPL09.WP4.047760 |
RPL09.Conn BE ISP DHA.CFD4 (RSL) FTSW > STSW EX384f [Across-Row] | Across-Row | Not Started | 10/25/27 | 10/27/27 | 3.8 | 3.8 |
|
218.8 |
RPL09.WP4.047800 |
RPL09.Conn BE ISP DHA.CFD5 (RSL) FTSW > STSW EX384f [In-Row] | In-Row | Not Started | 10/25/27 | 10/27/27 | 3.8 | 3.8 |
|
218.8 |
GCD.RPL09.4205 |
[RPL09] TC-C Ready : EF Pathways complete [DHD] | TC-C Ready: Production Cabling - DHD | Not Started | 10/26/27 | 10/26/27 | 0.0 | 0.0 |
|
302.5 |
GCD.RPL09.4245 |
[RPL09] TC-C Ready : Overhead cable tray complete [DHD] | TC-C Ready: Production Cabling - DHD | Not Started | 10/26/27 | 10/26/27 | 0.0 | 0.0 |
|
302.5 |
RPL.09.D.93840.XR20 |
100MW Redundant Power | Receive Milestones (XREFs) | Not Started | 10/26/27 | 10/26/27 | 0.0 | 0.0 |
|
241.2 |
RPL09.INT.CTRC.01490 |
RPL09.Interior.Center-Corridor (N) - Final Punch Walk | Fit out (North) | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
90.0 |
RPL09.INT.EC.9140 |
RPL09.Interior.ECr LO #14 - Install DAS (Distribution Antenna System) | Remaining of LO Wall #14 (Ancillary, Elec Room, Humidifier Room & IDF) | Not Started | 10/26/27 | 10/26/27 | 1.2 | 1.2 |
|
170.0 |
RPL09.INT.EC.9160 |
RPL09.Interior.ECr LO #14 - Install Flooring Tiles/Resinous Flooring in specific rooms **?? | Remaining of LO Wall #14 (Ancillary, Elec Room, Humidifier Room & IDF) | Not Started | 10/26/27 | 10/28/27 | 3.8 | 3.8 |
|
176.2 |
RPL09.INT.EC.LO.9180 |
RPL09.Interior.EC LO #14 - Electrical Trim Out | Interior Leave Out Wall #14 DHD/EC for DHB&D HACs | Not Started | 10/26/27 | 10/26/27 | 1.2 | 1.2 |
|
151.2 |
RPL09.INT.EC.LO.9200 |
RPL09.Interior.EC LO #14 - Security Trim Out | Interior Leave Out Wall #14 DHD/EC for DHB&D HACs | Not Started | 10/26/27 | 10/26/27 | 1.2 | 1.2 |
|
151.2 |
RPL09.INT.ENDC.5640 |
RPL09.Interior.EC Ext. Leave Out #18 - Tape Finish Paint | Exterior Leave Out Wall #18 EC - North for DHB&D HACs | Not Started | 10/26/27 | 11/01/27 | 6.2 | 6.2 |
|
138.8 |
RPL09.PR.DHB.FE.0010 |
RPL09.PR.DHB FENW Data Hall B - Provisioning - WBS Summary | FENW | Not Started | 10/26/27 | 03/10/28 | 113.8 | 113.8 |
|
165.0 |
RPL09.PR.DHB.FE.0015 |
RPL09.PR.DHB FENW PZ1 (Row 01-08) - ENS Ready for PZ1 | FENW | Not Started | 10/26/27 | 10/26/27 | 0.0 | 0.0 |
|
143.8 |
RPL09.PR.DHB.FE.0020 |
RPL09.PR.DHB FENW PZ1 (Row 01-08) - Provisioning, Auditing, Issue Remediation (FSW, SSW) | FENW | Not Started | 10/26/27 | 11/23/27 | 25.0 | 25.0 |
|
241.2 |
RPL09.SKN.E.LO.04060 |
RPL09.SKIN.LO#19 - Stemwall Water Proofing | Build back Exterior Leave Out Walls #19 (EC - South) | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
121.2 |
RPL09.WP3B.017720 |
RPL09.Conn EF2<>DHA.08 Test Pigtails (384F) P2&3 (MES) | EF2<>DHA.08 | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
133.8 |
RPL09.WP4.016020 |
RPL09.Conn DHA.06 Install (A-End) Ext. Trunk (384F) [SSW<>JXSW] | SSW<>JXSW | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
136.2 |
RPL09.WP4.016260 |
RPL09.Conn DHA.06 Install (A-End) Trunk (192F) [FSW<>SSW] | FSW<>SSW | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
138.8 |
RPL09.WP4.016780 |
RPL09.Conn DHA.06 Install (A-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/26/27 | 10/29/27 | 5.0 | 5.0 |
|
138.8 |
RPL09.WP4.018020 |
RPL09.Conn DHA.06.21 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
146.2 |
RPL09.WP4.020020 |
RPL09.Conn DHA.06.22 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
146.2 |
RPL09.WP4.021940 |
RPL09.Conn DHA.06.23 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
146.2 |
RPL09.WP4.025640 |
RPL09.Conn DHC.22 Install (A-End) Ext. Trunk (384F) [SSW<>JXSW] | SSW<>JXSW | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
222.5 |
RPL09.WP4.026000 |
RPL09.Conn DHC.22 Install (A-End) Trunk (192F) [FSW<>SSW] | FSW<>SSW | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
225.0 |
RPL09.WP4.026620 |
RPL09.Conn DHC.22 Install (A-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/26/27 | 10/29/27 | 5.0 | 5.0 |
|
225.0 |
RPL09.WP4.029440 |
RPL09.Conn DHC.22.05 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
232.5 |
RPL09.WP4.030640 |
RPL09.Conn DHB.15.17<>17 Install (Z-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | In-Row | Not Started | 10/26/27 | 10/26/27 | 1.2 | 1.2 |
|
135.0 |
RPL09.WP4.030660 |
RPL09.Conn DHB.16.21<>21 Install (Z-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | In-Row | Not Started | 10/26/27 | 10/26/27 | 1.2 | 1.2 |
|
135.0 |
RPL09.WP4.030880 |
RPL09.Conn DHB.16 Install (Z-End) Trunk (192F) [FSW<>SSW] | FSW<>SSW | Not Started | 10/26/27 | 10/27/27 | 2.5 | 2.5 |
|
130.0 |
RPL09.WP4.031580 |
RPL09.Conn DHB.15 Install (Z-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/26/27 | 10/29/27 | 5.0 | 5.0 |
|
132.5 |
RPL09.WP4.046960 |
RPL09.Conn BE ISP DHB.NC3 (RSL) FTSW>STSW TYP NC-EX288F (In Row Active>Passive Rack) | Network Core 3 | Not Started | 10/26/27 | 10/28/27 | 3.8 | 3.8 |
|
285.0 |
RPL06.SUCC |
SUCC | Obsolete | Not Started | 10/27/27 | 10/27/27 | 0.0 | 0.0 |
|
0.0 |
RPL06.SUCC |
SUCC | Obsolete | Not Started | 10/27/27 | 10/27/27 | 0.0 | 0.0 |
|
0.0 |
RPL06.SUCC |
SUCC | Obsolete | Not Started | 10/27/27 | 10/27/27 | 0.0 | 0.0 |
|
0.0 |
RPL06.SUCC |
SUCC | Obsolete | Not Started | 10/27/27 | 10/27/27 | 0.0 | 0.0 |
|
0.0 |
RPL09.CON.WP4.06600 |
RPL09.Conn WP4 FENW DHD CFD4 Infrastructure | Infrastructure | Not Started | 10/27/27 | 11/24/27 | 25.0 | 25.0 |
|
208.8 |
RPL09.CON.WP4.08200 |
RPL09.Conn WP4 FENW DHC CFD2 Infrastructure | Infrastructure | Not Started | 10/27/27 | 11/24/27 | 25.0 | 25.0 |
|
208.8 |
RPL09.CX.DHC.01070 |
RPL09.CX.DHC - L3/L4 - UPS Start-up | DHC ELECTRICAL | Not Started | 10/27/27 | 11/09/27 | 12.5 | 12.5 |
|
207.5 |
RPL09.CX.DHC.01380 |
RPL09.CX.DHC - L3/L4 - Control Fault Domain 03 - FW Flush and Fill | Control Fault Domain 3 | Not Started | 10/27/27 | 11/04/27 | 8.8 | 8.8 |
|
185.0 |
RPL09.EY.DHD.01390 |
RPL09.EY.DHD - Install Remaining EY Paving | Hardscape and Landscape | Not Started | 10/27/27 | 11/02/27 | 6.2 | 6.2 |
|
246.2 |
RPL09.EY.DHD.01400 |
RPL09.EY.DHD - Cure for Remaining Equipment Pads (High Early Mix) | Foundations | Not Started | 10/27/27 | 11/02/27 | 8.8 | 8.8 |
|
300.0 |
RPL09.EY.ENDC.1870 |
RPL09.EY.DHD.T2 - Demo of Tent | Tent 2 | Not Started | 10/27/27 | 11/09/27 | 12.5 | 12.5 |
|
225.0 |
RPL09.INT.DHC.01340 |
RPL09.Conn DHC - CFD2 - Set Passive Racks for WP#3b (16) | Infrastructure | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
177.5 |
RPL09.INT.DHC.01640 |
RPL09.Interior.DHC - Control Fault Domain 4 - Install Mechanical Side Aisle Cable Tray | Remaining Tie-ins post Mech Side Aisle install | Not Started | 10/27/27 | 11/24/27 | 25.0 | 25.0 |
|
152.5 |
RPL09.INT.DHC.01660 |
RPL09.Interior.DHC - Control Fault Domain 4 - Install copper from GS.IDF to BMS and EPMS panels (UG from Center IDF) | Remaining Tie-ins post Mech Side Aisle install | Not Started | 10/27/27 | 11/24/27 | 25.0 | 25.0 |
|
182.5 |
RPL09.INT.DHC.02610 |
RPL09.Conn DHC - CFD2 - Set Passive Racks for PON (16) | Infrastructure | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
205.0 |
RPL09.INT.DHD.01620 |
RPL09.Conn DHD - CFD4 - Set Passive Racks for WP#3b (16) | Infrastructure | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
177.5 |
RPL09.INT.DHD.01960 |
RPL09.Interior.DHD - Final Clean | Tie-Ins | Not Started | 10/27/27 | 11/01/27 | 5.0 | 5.0 |
|
247.5 |
RPL09.INT.DHD.02650 |
RPL09.Conn DHD - CFD4 - Set Passive Racks for PON (16) | Infrastructure | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
208.8 |
RPL09.INT.EC.9180 |
RPL09.Interior.ECr LO #14 - Install Remaining Lights | Remaining of LO Wall #14 (Ancillary, Elec Room, Humidifier Room & IDF) | Not Started | 10/27/27 | 11/01/27 | 5.0 | 5.0 |
|
170.0 |
RPL09.INT.EC.9380 |
RPL09.Interior.EC LO #15 - Frame Out All Walls | Remaining of LO #15 (Ancillary, Elec Room, Humidifier Room & IDF) | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
150.0 |
RPL09.INT.EC.LO.9340 |
RPL09.Interior.EC LO #15 - Install Mechanical Piping/ Refrigerant Lowside OH | Interior Leave Out Wall #15 DHC/EC for DHA&C HACs | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
140.0 |
RPL09.PR.DH.0010 |
RPL09 ENS Rooms Required for Start of Provisioning (ERAD, High Value Storage Room, Spoke Tech, Spoke Parts) | Connectivity Milestones | Not Started | 10/27/27 | 10/27/27 | 0.0 | 0.0 |
|
301.2 |
RPL09.WP3B.017740 |
RPL09.Conn EF2<>DHA.09 Test Pigtails (384F) P2&3 (MES) | EF2<>DHA.09 | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
132.5 |
RPL09.WP4.018780 |
RPL09.Conn DHA.07 Install (A-End) Ext. Trunk (384F) [SSW<>JXSW] | SSW<>JXSW | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
135.0 |
RPL09.WP4.019040 |
RPL09.Conn DHA.07 Install (A-End) Trunk (192F) [FSW<>SSW] | FSW<>SSW | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
137.5 |
RPL09.WP4.019380 |
RPL09.Conn DHA.07 Install (A-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/27/27 | 11/01/27 | 5.0 | 5.0 |
|
137.5 |
RPL09.WP4.020720 |
RPL09.Conn DHA.07.25 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
145.0 |
RPL09.WP4.022480 |
RPL09.Conn DHA.07.26 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
145.0 |
RPL09.WP4.024280 |
RPL09.Conn DHA.05.20 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
145.0 |
RPL09.WP4.024300 |
RPL09.Conn DHA.06.24 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
145.0 |
RPL09.WP4.025180 |
RPL09.Conn DHA.07.27 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
145.0 |
RPL09.WP4.025400 |
RPL09.Conn DHA.07.28 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 11/09/27 | 12.5 | 12.5 |
|
132.5 |
RPL09.WP4.025420 |
RPL09.Conn DHA.08.32 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/27/27 | 11/09/27 | 12.5 | 12.5 |
|
132.5 |
RPL09.WP4.030860 |
RPL09.Conn DHA.04 Install (Z-End) Trunk (192F) [FSW<>SSW] | FSW<>SSW | Not Started | 10/27/27 | 10/28/27 | 2.5 | 2.5 |
|
140.0 |
RPL09.WP4.031100 |
RPL09.Conn DHB.15.19<>19 Install (Z-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | In-Row | Not Started | 10/27/27 | 10/27/27 | 1.2 | 1.2 |
|
135.0 |
RPL09.WP4.031120 |
RPL09.Conn DHB.16.23<>23 Install (Z-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | In-Row | Not Started | 10/27/27 | 10/27/27 | 1.2 | 1.2 |
|
135.0 |
RPL09.WP4.031540 |
RPL09.Conn DHA.03 Install (Z-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/27/27 | 11/01/27 | 5.0 | 5.0 |
|
142.5 |
RPL09.WP4.033700 |
RPL09.Conn DHD.33.19<>19 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 10/27/27 | 10/27/27 | 1.2 | 1.2 |
|
231.2 |
RPL09.WP4.033880 |
RPL09.Conn DHD.33.18<>17 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
221.2 |
RPL09.WP4.034040 |
RPL09.Conn DHD.34.23<>23 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 10/27/27 | 10/27/27 | 1.2 | 1.2 |
|
231.2 |
RPL09.WP4.034480 |
RPL09.Conn DHD.34.22<>21 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 10/27/27 | 10/29/27 | 3.8 | 3.8 |
|
221.2 |
RPL06.SUCC |
SUCC | Obsolete | Not Started | 10/28/27 | 10/28/27 | 0.0 | 0.0 |
|
0.0 |
RPL09.CON.WP2.09140 |
RPL09.Conn - CorpNet & FacNet Available (DH D) - All IDFs | WP#02 GS | Not Started | 10/28/27 | 10/28/27 | 0.0 | 0.0 |
|
300.0 |
RPL09.CON.WP4.010020 |
RPL09.Conn A CFD4 - Deliver & Install - ORV3N (Loading at Night) | OFE- Passive In-row Racks, Racks (ORv3Ns, MCRs) & PON | Not Started | 10/28/27 | 11/08/27 | 10.0 | 10.0 |
|
116.2 |
RPL09.CON.WP4.010040 |
RPL09.Conn A CFD4 - Deliver & Assemble - PON | OFE- Passive In-row Racks, Racks (ORv3Ns, MCRs) & PON | Not Started | 10/28/27 | 11/08/27 | 10.0 | 10.0 |
|
131.2 |
RPL09.CX.CTRC.01000 |
RPL09.CX.Center COR - L3, L4, IST - WBS Summary | Center Corridor | Not Started | 10/28/27 | 01/13/28 | 62.5 | 62.5 |
|
90.0 |
RPL09.CX.CTRC.01010 |
RPL09.CX.Center COR - L3 | Center Corridor | Not Started | 10/28/27 | 12/13/27 | 37.5 | 37.5 |
|
90.0 |
RPL09.Conn.MS.01040 |
RPL09.Conn Wifi Ready - DH D (Pred from RPL10 CorpNet needed?) | Connectivity Milestones | Not Started | 10/28/27 | 10/28/27 | 0.0 | 0.0 |
|
242.5 |
RPL09.INT.EC.LO.9220 |
RPL09.Interior.EC LO #14 - Plumbing Trim Out | Interior Leave Out Wall #14 DHD/EC for DHB&D HACs | Not Started | 10/28/27 | 10/28/27 | 1.2 | 1.2 |
|
151.2 |
RPL09.INT.EC.LO.9240 |
RPL09.Interior.EC LO #14 - Fire Life Safety Trim Out | Interior Leave Out Wall #14 DHD/EC for DHB&D HACs | Not Started | 10/28/27 | 10/28/27 | 1.2 | 1.2 |
|
151.2 |
RPL09.SKN.E.LO.04080 |
RPL09.SKIN.LO#19 - Install IMP Flashing | Build back Exterior Leave Out Walls #19 (EC - South) | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
121.2 |
RPL09.WP3B.017760 |
RPL09.Conn EF2<>DHA.10 Test Pigtails (384F) P2&3 (MES) | EF2<>DHA.10 | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
131.2 |
RPL09.WP4.018800 |
RPL09.Conn DHA.08 Install (A-End) Ext. Trunk (384F) [SSW<>JXSW] | SSW<>JXSW | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
133.8 |
RPL09.WP4.019060 |
RPL09.Conn DHA.08 Install (A-End) Trunk (192F) [FSW<>SSW] | FSW<>SSW | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
136.2 |
RPL09.WP4.019400 |
RPL09.Conn DHA.08 Install (A-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/28/27 | 11/02/27 | 5.0 | 5.0 |
|
136.2 |
RPL09.WP4.020740 |
RPL09.Conn DHA.08.29 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
143.8 |
RPL09.WP4.022500 |
RPL09.Conn DHA.08.30 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
143.8 |
RPL09.WP4.025200 |
RPL09.Conn DHA.08.31 Install (A-End) Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
143.8 |
RPL09.WP4.031600 |
RPL09.Conn DHB.16 Install (Z-End) Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 10/28/27 | 11/02/27 | 5.0 | 5.0 |
|
130.0 |
RPL09.WP4.031960 |
RPL09.Conn DHC.21.04<>03 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 10/28/27 | 10/28/27 | 1.2 | 1.2 |
|
227.5 |
RPL09.WP4.031980 |
RPL09.Conn DHC.22.08<>07 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 10/28/27 | 10/28/27 | 1.2 | 1.2 |
|
227.5 |
RPL09.WP4.033220 |
RPL09.Conn DHA.05.18<>17 Install (Z-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 10/28/27 | 10/28/27 | 1.2 | 1.2 |
|
141.2 |
RPL09.WP4.033240 |
RPL09.Conn DHA.06.22<>21 Install (Z-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 10/28/27 | 10/28/27 | 1.2 | 1.2 |
|
141.2 |
RPL09.WP4.033520 |
RPL09.Conn DHA.05 Install (Z-End) Ext. Trunk (384F) [SSW<>JXSW] | SSW<>JXSW | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
136.2 |
RPL09.WP4.033540 |
RPL09.Conn DHA.06 Install (Z-End) Ext. Trunk (384F) [SSW<>JXSW] | SSW<>JXSW | Not Started | 10/28/27 | 10/29/27 | 2.5 | 2.5 |
|
136.2 |
RPL09.WP4.047820 |
RPL09.Conn BE ISP DHA.CFD5 (RSL) FTSW > STSW EX384f [Across-Row] | Across-Row | Not Started | 10/28/27 | 11/01/27 | 3.8 | 3.8 |
|
218.8 |
RPL09.CX.SSBC.01050 |
RPL09.CX.SSB COR - IST | SSB Corridor | Not Started | 10/29/27 | 11/12/27 | 12.5 | 12.5 |
|
138.8 |