Schedule Viewer

Last schedule upload: D3-R25005-00-RPL06 — 6139 activities — 04/16/2026 08:19 AM CT
RPL07 - GC LIVE SCHEDULE - Data Date 2026.04.12.xer · Uploaded Apr 16, 2026 01:16 PM · 5237 activities
Experimental Auto-populate checklist dates from schedule:
Clear
100
Activities Shown
0
Completed
0
In Progress
0
Critical
Activity ID Activity Name WBS Status Start Finish Dur (d) Rem (d) % Comp Float (d)
RPL07.INT.DHB.01900 RPL07.Interior.DHB - Control Fault Domain 5 - Install copper from GS.IDF to BMS and EPMS panels (UG from Corr IDF) Remaining Tie-ins post Mech Side Aisle install Not Started 02/05/27 03/05/27 25.0 25.0
0%
47.5
RPL07.INT.DHC.02290 RPL07.Interior.DHC - OFE - Control Fault Domain 1 (HAC) Control Fault Domain 1 Not Started 02/05/27 02/26/27 18.8 18.8
0%
46.2
RPL07.INT.ENDC.1940 RPL07.Interior.End-Corridor - BoW - Install Vertical Tube Steel for Cable Tray (IFP Add) Balance of Walls & Overhead Not Started 02/05/27 02/10/27 5.0 5.0
0%
125.0
RPL07.WP3B.017860 RPL07.Conn EF2<>DHB.15 Test Pigtails (384F) P2&3 (LV) EF2<>DHB.15 Not Started 02/05/27 02/08/27 2.5 2.5
0%
115.0
GCD.RPL07.4125 [RPL07] TC-C Ready : Production Cabling Start [DHA Rows 17-24] TC-C Ready: Production Cabling - DHA Not Started 02/08/27 02/08/27 0.0 0.0
0%
286.2
RPL07.CON.WP2.13060 RPL07.Conn - GSMDF1(South)<>DH A - CFD3 Rack #50 Pull, Install & Patch PON Trunks MDF1 <> DH A - Rack#50 LV side Not Started 02/08/27 02/12/27 6.2 6.2
0%
113.8
RPL07.CON.WP2.14060 RPL07.Conn - GSMDF2(North)<>DH A - CFD3 Rack #01 Pull, Install & Test PON Trunks MDF2 <> DH A - Rack#01 MES side Not Started 02/08/27 02/10/27 3.8 3.8
0%
121.2
RPL07.CON.WP3A.01000 RPL07.Conn - OSP - WBS Summary WP#3A OSP Not Started 02/08/27 04/09/27 53.8 53.8
0%
232.5
RPL07.CON.WP3A.01200 RPL07.Conn - Production EF2 (North) - WBS Summary Prod EF2 (North) Not Started 02/08/27 03/25/27 41.2 41.2
0%
245.0
RPL07.CON.WP3A.01620 RPL07.Conn EF2 (North) Infrastructure 1 (Racks & Vertical Cable Manager, Ladder Racks) Infrastructure Not Started 02/08/27 03/08/27 25.0 25.0
0%
77.5
RPL07.CON.WP3B.02080 RPL07.Conn EF1<>DHA.05 - WBS Summary EF1<>DHA.05 Not Started 02/08/27 02/22/27 12.5 12.5
0%
113.8
RPL07.CX.DHB.01120 RPL07.CX.DHB - L3/L4 - Control Fault Domain 02 Control Fault Domain 2 Not Started 02/08/27 03/02/27 20.0 20.0
0%
23.8
RPL07.CX.DHB.01210 RPL07.CX.DHB - L3/L4 - Remaining Mechanical Equipment DHB MECHANICAL Not Started 02/08/27 02/12/27 6.2 6.2
0%
103.8
RPL07.INT.CTRC.06960 RPL07.Interior.Center-Corridor - Final Finishes & Fixtures - MEP Trims Restrooms Not Started 02/08/27 02/17/27 8.8 8.8
0%
36.2
RPL07.INT.CTRC.3000 RPL07.Interior.Center-Corridor LO #10 & #12 - Install Electrical Lowside OH Interior Leave Out Wall #10, #12 (DHB/CC) Not Started 02/08/27 02/11/27 5.0 5.0
0%
41.2
RPL07.INT.CTRC.7960 RPL07.Interior.Center-Corridor LO #10 - Backing Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 02/08/27 02/09/27 2.5 2.5
0%
51.2
RPL07.INT.DHD.01130 RPL07.Interior.DHD - Control Fault Domain 1 - Install Duct (MES Side) Remaining Tie-ins post Mech Side Aisle install Not Started 02/08/27 03/08/27 25.0 25.0
0%
70.0
RPL07.INT.DHD.01140 RPL07.Interior.DHD - Control Fault Domain 1 - Install Vesda / FA Remaining Tie-ins post Mech Side Aisle install Not Started 02/08/27 03/08/27 25.0 25.0
0%
82.5
RPL07.INT.DHD.01150 RPL07.Interior.DHD - Control Fault Domain 1 - Install FW Remaining Tie-ins post Mech Side Aisle install Not Started 02/08/27 03/08/27 25.0 25.0
0%
70.0
RPL07.INT.DHD.01990 RPL07.Interior.DHD - Control Fault Domain 1 - Install TW Remaining Tie-ins post Mech Side Aisle install Not Started 02/08/27 03/08/27 25.0 25.0
0%
70.0
RPL07.INT.SSB.01640 RPL07.Interior.SSB - Loading Dock and Storage - Final Punch Walk Loading Dock and Storage Not Started 02/08/27 02/09/27 2.5 2.5
0%
127.5
RPL07.WP3B.011180 RPL07.Conn EF1<>DHA.01 Pull Pigtails (384F) P1&4 (LV) EF1<>DHA.05 Not Started 02/08/27 02/08/27 1.2 1.2
0%
105.0
RPL07.WP4.015400 RPL07.Conn DHA.05 Pull Ext. Trunk (384F) [SSW<>JXSW] SSW<>JXSW Not Started 02/08/27 02/08/27 1.2 1.2
0%
123.8
RPL07.WP4.015420 RPL07.Conn DHA.06 Pull Ext. Trunk (384F) [SSW<>JXSW] SSW<>JXSW Not Started 02/08/27 02/08/27 1.2 1.2
0%
123.8
RPL07.WP4.015800 RPL07.Conn DHA.05.17 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 02/08/27 02/22/27 12.5 12.5
0%
86.2
RPL07.WP4.015820 RPL07.Conn DHA.06.21 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 02/08/27 02/22/27 12.5 12.5
0%
86.2
RPL07.WP4.016120 RPL07.Conn DHB.15.18 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 02/08/27 02/22/27 12.5 12.5
0%
86.2
RPL07.WP4.016140 RPL07.Conn DHB.16.22 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 02/08/27 02/22/27 12.5 12.5
0%
86.2
RPL07.WP4.016160 RPL07.Conn DHA.05 Pull Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 02/08/27 02/08/27 1.2 1.2
0%
115.0
RPL07.WP4.016180 RPL07.Conn DHA.06 Pull Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 02/08/27 02/08/27 1.2 1.2
0%
115.0
RPL07.WP4.016920 RPL07.Conn DHA.03.12<>11 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 02/08/27 02/08/27 1.2 1.2
0%
133.8
RPL07.WP4.016940 RPL07.Conn DHA.04.16<>15 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 02/08/27 02/08/27 1.2 1.2
0%
133.8
DCC.B7.3165 [SSDCB2] PortMaps Delivered : GS Connectivity Not Started 02/09/27 02/09/27 0.0 0.0
0%
285.0
DCC.B7.3170 [SSDCB2] PortMaps Delivered : Elevations & Cabling Connectivity Not Started 02/09/27 02/09/27 0.0 0.0
0%
285.0
DCC.B7.3175 [SSDCB2] PortMaps Delivered : Backbone Connectivity Not Started 02/09/27 02/09/27 0.0 0.0
0%
285.0
DCC.B7.3180 [SSDCB2] PortMaps Delivered : Front End Connectivity Not Started 02/09/27 02/09/27 0.0 0.0
0%
285.0
DCC.B7.3460 [SSDCB2] Production Dark Fiber Path 1 - Circuit Delivered **Pred?? only for RPL10?? Connectivity Not Started 02/09/27 02/09/27 0.0 0.0
0%
285.0
RPL07.CON.WP3B.02040 RPL07.Conn EF1<>DHA.06 - WBS Summary EF1<>DHA.06 Not Started 02/09/27 02/23/27 12.5 12.5
0%
112.5
RPL07.EY.SSB.01280 RPL07.EY.SSB - Install Curb and Gutter Hardscape and Landscape Not Started 02/09/27 02/23/27 12.5 12.5
0%
67.5
RPL07.INT.CTRC.3580 RPL07.Interior.Center-Corridor LO #11 - Install Remaining Vertical Tube Steel Support for Cable Tray (IFP Add) Remaining of LO Wall #11 (Spoke Parts) Not Started 02/09/27 02/10/27 2.5 2.5
0%
55.0
RPL07.INT.CTRC.3600 RPL07.Interior.Center-Corridor LO #11 & #13 - Install Mechanical Piping Lowside OH Interior Leave Out Wall #11, #13 (DHA/CC) Not Started 02/09/27 02/11/27 3.8 3.8
0%
12.5
RPL07.INT.CTRC.8340 RPL07.Interior.Center-Corridor LO #11 - Frame Out All Walls Remaining of LO Wall #11 (Spoke Parts) Not Started 02/09/27 02/11/27 3.8 3.8
0%
22.5
RPL07.WP3B.011200 RPL07.Conn EF1<>DHA.01 Pull Pigtails (384F) P1&4 (LV) EF1<>DHA.06 Not Started 02/09/27 02/09/27 1.2 1.2
0%
105.0
RPL07.WP3B.012620 RPL07.Conn EF1<>DHA.05 Install (A-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.05 Not Started 02/09/27 02/09/27 1.2 1.2
0%
113.8
RPL07.WP3B.017880 RPL07.Conn EF2<>DHB.16 Test Pigtails (384F) P2&3 (LV) EF2<>DHB.16 Not Started 02/09/27 02/10/27 2.5 2.5
0%
110.0
RPL07.WP4.015840 RPL07.Conn DHA.05 Pull Trunk (192F) [FSW<>SSW] FSW<>SSW Not Started 02/09/27 02/09/27 1.2 1.2
0%
123.8
RPL07.WP4.015860 RPL07.Conn DHA.06 Pull Trunk (192F) [FSW<>SSW] FSW<>SSW Not Started 02/09/27 02/09/27 1.2 1.2
0%
123.8
RPL07.WP4.016400 RPL07.Conn DHA.05.17<>17 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 02/09/27 02/11/27 3.8 3.8
0%
115.0
RPL07.WP4.016420 RPL07.Conn DHA.06.21<>21 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 02/09/27 02/11/27 3.8 3.8
0%
115.0
RPL07.WP4.016440 RPL07.Conn DHA.05 Install Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 02/09/27 02/11/27 3.8 3.8
0%
133.8
RPL07.WP4.016460 RPL07.Conn DHA.06 Install Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 02/09/27 02/11/27 3.8 3.8
0%
133.8
RPL07.WP4.016600 RPL07.Conn DHB.15.18<>17 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 02/09/27 02/09/27 1.2 1.2
0%
118.8
RPL07.WP4.016620 RPL07.Conn DHB.16.22<>21 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 02/09/27 02/09/27 1.2 1.2
0%
118.8
RPL07.WP4.016720 RPL07.Conn DHB.15.20<>19 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 02/09/27 02/12/27 5.0 5.0
0%
115.0
RPL07.WP4.016740 RPL07.Conn DHB.16.24<>23 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 02/09/27 02/12/27 5.0 5.0
0%
115.0
RPL07.CON.WP4.01600 RPL07.Conn WP4 FENW DHB CFD4 Infrastructure Infrastructure Not Started 02/10/27 03/10/27 25.0 25.0
0%
98.8
RPL07.CX.DHA.01560 RPL07.CX.DHA - L3/L4 - Control Fault Domain 04 - FW Flush and Fill Control Fault Domain 4 Not Started 02/10/27 02/19/27 8.8 8.8
0%
75.0
RPL07.INT.CTRC.01440 RPL07.Interior.Center-Corridor (N) - Plumbing Trim Fit out (North) Not Started 02/10/27 02/16/27 5.0 5.0
0%
67.5
RPL07.INT.CTRC.8280 RPL07.Interior.Center-Corridor LO #10 - Install Door Frame Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 02/10/27 02/11/27 2.5 2.5
0%
51.2
RPL07.INT.DHB.01700 RPL07.Conn DHB - CFD4 - Set Passive Racks for WP#3b (16) Infrastructure Not Started 02/10/27 02/12/27 3.8 3.8
0%
67.5
RPL07.INT.DHB.02860 RPL07.Conn DHB - CFD4 - Set Passive Racks for PON (16) Infrastructure Not Started 02/10/27 02/12/27 3.8 3.8
0%
96.2
RPL07.INT.DHC.02310 RPL07.Interior.DHC - OFE - Control Fault Domain 1 (Mech Side Aisle) Control Fault Domain 1 Not Started 02/10/27 03/01/27 16.2 16.2
0%
53.8
RPL07.INT.SSBC.01520 RPL07.Interior.SSB-Corridor - Remaining Mechanical DHA OFE TIe Ins Fit out Not Started 02/10/27 02/17/27 6.2 6.2
0%
111.2
RPL07.INT.SSBC.01530 RPL07.Interior.SSB-Corridor - Remaining DHB L2 Checklist Completion Fit out Not Started 02/10/27 02/17/27 6.2 6.2
0%
117.5
RPL07.INT.SSBC.01540 RPL07.Interior.SSB-Corridor - Remaining Electrical DHA OFE TIe Ins Fit out Not Started 02/10/27 02/17/27 6.2 6.2
0%
111.2
RPL07.WP3B.012640 RPL07.Conn EF1<>DHA.06 Install (A-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.06 Not Started 02/10/27 02/10/27 1.2 1.2
0%
112.5
RPL07.WP3B.014060 RPL07.Conn EF1<>DHA.05 Splice (A-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.05 Not Started 02/10/27 02/18/27 7.5 7.5
0%
113.8
RPL07.WP3B.015500 RPL07.Conn EF1<>DHA.05 Install (Z-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.05 Not Started 02/10/27 02/10/27 1.2 1.2
0%
113.8
RPL07.WP4.016200 RPL07.Conn DHA.05 Pull Trunk (384F) [RSW<>FSW] Trunks Not Started 02/10/27 02/11/27 2.5 2.5
0%
123.8
RPL07.WP4.016220 RPL07.Conn DHA.06 Pull Trunk (384F) [RSW<>FSW] Trunks Not Started 02/10/27 02/11/27 2.5 2.5
0%
123.8
GCD.RPL07.4665 L3/L4 Start - DHA Rows 17-24 DH Not Started 02/11/27 02/11/27 0.0 0.0
0%
118.8
RPL07.CON.WP2.08880 RPL07.Conn - GSIDF/DH A1 - Install & Test Network (FIM) Network Not Started 02/11/27 02/16/27 3.8 3.8
0%
278.8
RPL07.CX.DHA.01120 RPL07.CX.DHA - L3/L4 - Elec. Domain 05/06 DHA ELECTRICAL Not Started 02/11/27 02/17/27 5.0 5.0
0%
47.5
RPL07.INT.CTRC.07060 RPL07.Interior.Center-Corridor - Final Finishes & Fixtures - Flooring Restrooms Not Started 02/11/27 02/22/27 8.8 8.8
0%
41.2
RPL07.INT.CTRC.3720 RPL07.Interior.Center-Corridor LO #11 - Install Remaining Horizontal Steel Supports for Cable Tray (IFP Add) Remaining of LO Wall #11 (Spoke Parts) Not Started 02/11/27 02/16/27 3.8 3.8
0%
55.0
RPL07.INT.ENDC.1960 RPL07.Interior.End-Corridor - BoW - Install Horizontal Steel for Cable Tray (IFP Add) Balance of Walls & Overhead Not Started 02/11/27 02/17/27 5.0 5.0
0%
125.0
RPL07.INT.SSB.02600 RPL07.Interior.SSB - BoW - ACT - Close Up Inspection Balance of Walls and OverHead Not Started 02/11/27 02/18/27 6.2 6.2
0%
77.5
RPL07.WP3B.014080 RPL07.Conn EF1<>DHA.06 Splice (A-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.06 Not Started 02/11/27 02/19/27 7.5 7.5
0%
112.5
RPL07.WP3B.015520 RPL07.Conn EF1<>DHA.06 Install (Z-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.06 Not Started 02/11/27 02/11/27 1.2 1.2
0%
112.5
RPL07.INT.CTRC.01750 RPL07.Interior.Center-Corridor (S) - Fire Life Safe Trim Fit out (South) Not Started 02/12/27 02/18/27 5.0 5.0
0%
55.0
RPL07.INT.CTRC.01970 RPL07.Interior.Center-Corridor (S) - Set Equipment / Interior Fit out (South) Not Started 02/12/27 02/19/27 6.2 6.2
0%
22.5
RPL07.INT.CTRC.2780 RPL07.Interior.Center-Corridor LO #10 & #12 - Install Door Frames Interior Leave Out Wall #10, #12 (DHB/CC) Not Started 02/12/27 02/16/27 2.5 2.5
0%
41.2
RPL07.INT.CTRC.3620 RPL07.Interior.Center-Corridor LO #11 & #13 - Install Fire Life Safety Lowside OH Interior Leave Out Wall #11, #13 (DHA/CC) Not Started 02/12/27 02/17/27 3.8 3.8
0%
17.5
RPL07.INT.CTRC.3640 RPL07.Interior.Center-Corridor LO #11 & #13 - Install Plumbing Lowside OH Interior Leave Out Wall #11, #13 (DHA/CC) Not Started 02/12/27 02/17/27 3.8 3.8
0%
12.5
RPL07.INT.CTRC.7980 RPL07.Interior.Center-Corridor LO #10 - QC Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 02/12/27 02/12/27 1.2 1.2
0%
53.8
RPL07.INT.CTRC.8240 RPL07.Interior.Center-Corridor LO #10 - Fire Safing/ Wall Finishes Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 02/12/27 02/16/27 2.5 2.5
0%
51.2
RPL07.INT.CTRC.8360 RPL07.Interior.Center-Corridor LO #11 - Install Security Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 02/12/27 02/17/27 3.8 3.8
0%
45.0
RPL07.INT.CTRC.8380 RPL07.Interior.Center-Corridor LO #11 - Install Controls / EPMS / BMS OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 02/12/27 02/17/27 3.8 3.8
0%
45.0
RPL07.INT.CTRC.8400 RPL07.Interior.Center-Corridor LO #11 - Install Fire Life Safety Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 02/12/27 02/17/27 3.8 3.8
0%
45.0
RPL07.INT.CTRC.8420 RPL07.Interior.Center-Corridor LO #11 - Install Plumbing Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 02/12/27 02/17/27 3.8 3.8
0%
45.0
RPL07.INT.CTRC.8440 RPL07.Interior.Center-Corridor LO #11 - Install Mechanical Piping Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 02/12/27 02/17/27 3.8 3.8
0%
45.0
RPL07.INT.CTRC.8460 RPL07.Interior.Center-Corridor LO #11 - Install Electrical Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 02/12/27 02/22/27 7.5 7.5
0%
41.2
RPL07.INT.DHA.01720 RPL07.Interior.DHA - Control Fault Domain 5 - Pull BMS from panel to devices Remaining Tie-ins post Mech Side Aisle install Not Started 02/12/27 03/12/27 25.0 25.0
0%
53.8
RPL07.INT.DHA.01730 RPL07.Interior.DHA - Control Fault Domain 5 - Pull EMPS from panel to devices Remaining Tie-ins post Mech Side Aisle install Not Started 02/12/27 03/12/27 25.0 25.0
0%
53.8
RPL07.INT.DHA.01740 RPL07.Interior.DHA - Control Fault Domain 5 - Set UPS and Panel (2) Remaining Tie-ins post Mech Side Aisle install Not Started 02/12/27 03/12/27 25.0 25.0
0%
46.2
RPL07.INT.DHB.01990 RPL07.Interior.DHB - Control Fault Domain 5 - L2 Checklist Completion Remaining Tie-ins post Mech Side Aisle install Not Started 02/12/27 03/12/27 25.0 25.0
0%
47.5
RPL07.INT.DHD.02350 RPL07.Interior.DHD - OFE - Control Fault Domain 2 (HAC) Control Fault Domain 2 Not Started 02/12/27 02/26/27 12.5 12.5
0%
30.0
RPL07.WP4.017260 RPL07.Conn DHA.05.19<>19 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 02/12/27 02/17/27 3.8 3.8
0%
115.0
RPL07.WP4.017280 RPL07.Conn DHA.06.23<>23 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 02/12/27 02/17/27 3.8 3.8
0%
115.0
GCD.RPL07.3530 [RPL07] TC-C Ready : Production Cabling Start [DHB Rows 25-32] TC-C Ready: Production Cabling - DHB Not Started 02/16/27 02/16/27 0.0 0.0
0%
280.0