| Activity ID | Activity Name | WBS | Status | Start | Finish | Dur (d) | Rem (d) | % Comp | Float (d) |
|---|---|---|---|---|---|---|---|---|---|
RPL06.CON.WP2.08840 |
RPL06.Conn - GSIDF/DH A1 - Install Infrastructure (Racks, Waterfalls etc.) | Infrastructure | Not Started | 11/03/26 | 11/06/26 | 5.0 | 5.0 |
|
137.5 |
RPL06.CON.WP2.11020 |
RPL06.Conn - GSMDF1(South)<>DH B - CFD1 Rack #01 Pull, Install & Test PON Trunks | MDF1 <> DH B - Rack#01 MES side | Not Started | 11/03/26 | 11/05/26 | 3.8 | 3.8 |
|
126.2 |
RPL06.CON.WP2.12020 |
RPL06.Conn - GSMDF2(North)<>DH B - CFD1 Rack #50 Pull, Install & Test PON Trunks | MDF2 <> DH B - Rack#50 LV side | Not Started | 11/03/26 | 11/05/26 | 3.8 | 3.8 |
|
126.2 |
RPL06.CON.WP2.13020 |
RPL06.Conn - GSMDF1(South)<>DH A - CFD1 Rack #50 Pull, Install & Test PON Trunks | MDF1 <> DH A - Rack#50 LV side | Not Started | 11/03/26 | 11/05/26 | 3.8 | 3.8 |
|
138.8 |
RPL06.CON.WP2.14020 |
RPL06.Conn - GSMDF2(North)<>DH A - CFD1 Rack #01 Pull, Install & Test PON Trunks | MDF2 <> DH A - Rack#01 MES side | Not Started | 11/03/26 | 11/05/26 | 3.8 | 3.8 |
|
138.8 |
RPL06.CON.WP3B.01240 |
RPL06.Conn EF2<>DHB.16 - WBS Summary | EF2<>DHB.16 | Not Started | 11/03/26 | 11/18/26 | 13.8 | 13.8 |
|
118.8 |
RPL06.INT.ENDC.1600 |
RPL06.Interior.End-Corridor - BoW - Electrical Trim Out | Balance of Walls & Overhead | Not Started | 11/03/26 | 11/12/26 | 8.8 | 8.8 |
|
131.2 |
RPL06.INT.ENDC.1620 |
RPL06.Interior.End-Corridor - BoW - Security Trim Out | Balance of Walls & Overhead | Not Started | 11/03/26 | 11/12/26 | 8.8 | 8.8 |
|
131.2 |
RPL06.INT.ENDC.1640 |
RPL06.Interior.End-Corridor - BoW - Duct Drops / Trim out | Balance of Walls & Overhead | Not Started | 11/03/26 | 11/09/26 | 6.2 | 6.2 |
|
131.2 |
RPL06.INT.ENDC.1740 |
RPL06.Interior.End-Corridor - BoW - Install Remaining Lights | Balance of Walls & Overhead | Not Started | 11/03/26 | 11/17/26 | 12.5 | 12.5 |
|
150.0 |
RPL06.INT.ENDC.1980 |
RPL06.Interior.End-Corridor - BoW - Install Balance Of Refrigerant Line | Balance of Walls & Overhead | Not Started | 11/03/26 | 11/09/26 | 6.2 | 6.2 |
|
158.8 |
RPL06.INT.SSB.14640 |
RPL06.Interior.SSB LO #01 to #05 - Electrical L2 Checklist Completion | Finishes | Not Started | 11/03/26 | 11/17/26 | 12.5 | 12.5 |
|
72.5 |
RPL06.INT.SSBC.01310 |
RPL06.Interior.SSB-Corridor - Install Lighting | Fit out | Not Started | 11/03/26 | 11/12/26 | 8.8 | 8.8 |
|
67.5 |
RPL06.WP3B.012120 |
RPL06.Conn EF2<>DHB.16 Pull Pigtails (384F) P2&3 (LV) | EF2<>DHB.16 | Not Started | 11/03/26 | 11/04/26 | 2.5 | 2.5 |
|
66.2 |
RPL06.WP3B.013540 |
RPL06.Conn EF2<>DHB.15 Install (A-End) Pigtails (384F) P2&3 (LV) | EF2<>DHB.15 | Not Started | 11/03/26 | 11/03/26 | 1.2 | 1.2 |
|
76.2 |
RPL06.WP3B.014040 |
RPL06.Conn EF1<>DHA.04 Splice (A-End) Pigtails (384F) P1&4 (LV) | EF1<>DHA.04 | Not Started | 11/03/26 | 11/10/26 | 7.5 | 7.5 |
|
135.0 |
RPL06.WP3B.015480 |
RPL06.Conn EF1<>DHA.04 Install (Z-End) Pigtails (384F) P1&4 (LV) | EF1<>DHA.04 | Not Started | 11/03/26 | 11/03/26 | 1.2 | 1.2 |
|
135.0 |
RPL06.WP4.014360 |
RPL06.Conn DHB.15 Pull Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 11/03/26 | 11/03/26 | 1.2 | 1.2 |
|
88.8 |
RPL06.WP4.014380 |
RPL06.Conn DHB.16 Pull Trunk (384F) [RSW<>FSW] | Trunks | Not Started | 11/03/26 | 11/03/26 | 1.2 | 1.2 |
|
133.8 |
RPL06.WP4.014640 |
RPL06.Conn DHA.03.09<>09 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/03/26 | 11/03/26 | 1.2 | 1.2 |
|
153.8 |
RPL06.WP4.014660 |
RPL06.Conn DHA.04.13<>13 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/03/26 | 11/03/26 | 1.2 | 1.2 |
|
153.8 |
RPL06.WP4.014760 |
RPL06.Conn DHA.03.11<>11 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/03/26 | 11/05/26 | 3.8 | 3.8 |
|
138.8 |
RPL06.WP4.014780 |
RPL06.Conn DHA.04.15<>15 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/03/26 | 11/05/26 | 3.8 | 3.8 |
|
138.8 |
GCD.RPL06.2607 |
L3/L4 Start - DHB Rows 17-24 | DH | Not Started | 11/04/26 | 11/04/26 | 0.0 | 0.0 |
|
127.5 |
RPL06.CX.DHB.01110 |
RPL06.CX.DHB - L3/L4 - Elec. Domain 05/06 | DHB ELECTRICAL | Not Started | 11/04/26 | 11/09/26 | 5.0 | 5.0 |
|
41.2 |
RPL06.CX.DHB.01560 |
RPL06.CX.DHB - L3/L4 - Control Fault Domain 04 - FW Flush and Fill | Control Fault Domain 4 | Not Started | 11/04/26 | 11/13/26 | 8.8 | 8.8 |
|
47.5 |
RPL06.INT.CTRC.06900 |
RPL06.Interior.Center-Corridor - Final Finishes & Fixtures - Casework | Restrooms | Not Started | 11/04/26 | 11/13/26 | 8.8 | 8.8 |
|
37.5 |
RPL06.INT.CTRC.1360 |
RPL06.Interior.Center-Corridor - BoW - Install Split Systems/Humidifiers | Balance of Walls & Overhead | Not Started | 11/04/26 | 11/10/26 | 6.2 | 6.2 |
|
73.8 |
RPL06.WP3B.014980 |
RPL06.Conn EF2<>DHB.15 Splice (A-End) Pigtails (384F) P2&3 (LV) | EF2<>DHB.15 | Not Started | 11/04/26 | 11/12/26 | 7.5 | 7.5 |
|
76.2 |
RPL06.WP3B.016420 |
RPL06.Conn EF2<>DHB.15 Install (Z-End) Pigtails (384F) P2&3 (LV) | EF2<>DHB.15 | Not Started | 11/04/26 | 11/04/26 | 1.2 | 1.2 |
|
76.2 |
RPL06.WP4.014600 |
RPL06.Conn DHA.01.03 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 11/04/26 | 11/18/26 | 12.5 | 12.5 |
|
128.8 |
RPL06.WP4.014620 |
RPL06.Conn DHA.02.07 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 11/04/26 | 11/18/26 | 12.5 | 12.5 |
|
128.8 |
RPL06.WP4.014960 |
RPL06.Conn DHB.11.04 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 11/04/26 | 11/18/26 | 12.5 | 12.5 |
|
128.8 |
RPL06.WP4.014980 |
RPL06.Conn DHB.12.08 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 11/04/26 | 11/18/26 | 12.5 | 12.5 |
|
128.8 |
RPL06.CON.WP2.08700 |
RPL06.Conn - CorpNet & FacNet Available (DH B) - all IDFS | WP#02 GS | Not Started | 11/05/26 | 11/05/26 | 0.0 | 0.0 |
|
327.5 |
RPL06.Conn.MS.01000 |
RPL06.Conn Wifi Ready - DH B (Pred from RPL10 CorpNet needed?) | Connectivity Milestones | Not Started | 11/05/26 | 11/05/26 | 0.0 | 0.0 |
|
137.5 |
RPL06.INT.CTRC.2560 |
RPL06.Interior.Center-Corridor LO #10 - Install Vertical Tube Steel Support for Cable Tray (IFP Add) | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/05/26 | 11/06/26 | 2.5 | 2.5 |
|
31.2 |
RPL06.INT.CTRC.2660 |
RPL06.Interior.Center-Corridor LO #10 & #12 - Install Mechanical Piping Lowside OH | Interior Leave Out Wall #10, #12 (DHB/CC) | Not Started | 11/05/26 | 11/09/26 | 3.8 | 3.8 |
|
2.5 |
RPL06.INT.CTRC.7760 |
RPL06.Interior.Center-Corridor LO #10 - Frame Out All Remaining Walls | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/05/26 | 11/09/26 | 3.8 | 3.8 |
|
56.2 |
RPL06.INT.DHA.03760 |
RPL06.Interior.DHA - OFE - Control Fault Domain 5 (Mech Side Aisle) | Control Fault Domain 5 | Not Started | 11/05/26 | 11/19/26 | 12.5 | 12.5 |
|
8.8 |
RPL06.INT.DHD.02310 |
RPL06.Interior.DHD - OFE - Control Fault Domain 1 (Mech Side Aisle) | Control Fault Domain 1 | Not Started | 11/05/26 | 11/20/26 | 13.8 | 13.8 |
|
20.0 |
RPL06.INT.ENDC.1700 |
RPL06.Interior.End-Corridor - BoW - Plumbing Trim Out | Balance of Walls & Overhead | Not Started | 11/05/26 | 11/12/26 | 6.2 | 6.2 |
|
131.2 |
RPL06.INT.ENDC.1720 |
RPL06.Interior.End-Corridor - BoW - Fire Life Safety Trim Out / Fire Alarm Trim Out | Balance of Walls & Overhead | Not Started | 11/05/26 | 11/16/26 | 8.8 | 8.8 |
|
131.2 |
RPL06.INT.SBC.03980 |
RPL06.Interior.SSB-Corridor - BoW - Install Flooring Tiles/Resinous Flooring in specific rooms | Balance of Walls & Overhead | Not Started | 11/05/26 | 11/16/26 | 8.8 | 8.8 |
|
63.8 |
RPL06.INT.SBC.06500 |
RPL06.Interior.SSB-Corridor - BoW - QC | Balance of Walls & Overhead | Not Started | 11/05/26 | 11/12/26 | 6.2 | 6.2 |
|
66.2 |
RPL06.INT.SSB.01630 |
RPL06.Interior.SSB - Loading Dock and Storage - Final Clean | Loading Dock and Storage | Not Started | 11/05/26 | 11/10/26 | 5.0 | 5.0 |
|
138.8 |
RPL06.INT.SSBC.01490 |
RPL06.Interior.SSB-Corridor - Remaining Mechanical DHB OFE TIe Ins | Fit out | Not Started | 11/05/26 | 11/12/26 | 6.2 | 6.2 |
|
130.0 |
RPL06.INT.SSBC.01500 |
RPL06.Interior.SSB-Corridor - Remaining Electrical DHB OFE TIe Ins | Fit out | Not Started | 11/05/26 | 11/12/26 | 6.2 | 6.2 |
|
130.0 |
RPL06.WP3B.013560 |
RPL06.Conn EF2<>DHB.16 Install (A-End) Pigtails (384F) P2&3 (LV) | EF2<>DHB.16 | Not Started | 11/05/26 | 11/05/26 | 1.2 | 1.2 |
|
118.8 |
RPL06.WP4.015120 |
RPL06.Conn DHB.15.17<>17 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/05/26 | 11/05/26 | 1.2 | 1.2 |
|
138.8 |
RPL06.WP4.015140 |
RPL06.Conn DHB.16.21<>21 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/05/26 | 11/05/26 | 1.2 | 1.2 |
|
138.8 |
RPL06.WP4.015200 |
RPL06.Conn DHB.15.19<>19 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/05/26 | 11/09/26 | 3.8 | 3.8 |
|
123.8 |
RPL06.WP4.015220 |
RPL06.Conn DHB.16.23<>23 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/05/26 | 11/09/26 | 3.8 | 3.8 |
|
123.8 |
RPL06.CON.WP2.11040 |
RPL06.Conn - GSMDF1(South)<>DH B - CFD2 Rack #01 Pull, Install & Test PON Trunks | MDF1 <> DH B - Rack#01 MES side | Not Started | 11/06/26 | 11/10/26 | 3.8 | 3.8 |
|
126.2 |
RPL06.CON.WP2.12040 |
RPL06.Conn - GSMDF2(North)<>DH B - CFD2 Rack #50 Pull, Install & Test PON Trunks | MDF2 <> DH B - Rack#50 LV side | Not Started | 11/06/26 | 11/10/26 | 3.8 | 3.8 |
|
126.2 |
RPL06.CON.WP2.13040 |
RPL06.Conn - GSMDF1(South)<>DH A - CFD2 Rack #50 Pull, Install & Test PON Trunks | MDF1 <> DH A - Rack#50 LV side | Not Started | 11/06/26 | 11/10/26 | 3.8 | 3.8 |
|
138.8 |
RPL06.CON.WP2.14040 |
RPL06.Conn - GSMDF2(North)<>DH A - CFD2 Rack #01 Pull, Install & Test PON Trunks | MDF2 <> DH A - Rack#01 MES side | Not Started | 11/06/26 | 11/10/26 | 3.8 | 3.8 |
|
138.8 |
RPL06.EY.DHA.01470 |
RPL06.EY.DHA - Remaining L2 Checklist Completion | Tie-ins | Not Started | 11/06/26 | 11/13/26 | 6.2 | 6.2 |
|
125.0 |
RPL06.INT.DHA.01640 |
RPL06.Interior.DHA - Control Fault Domain 4 - Install Mechanical Side Aisle Cable Tray | Remaining Tie-ins post Mech Side Aisle install | Not Started | 11/06/26 | 12/01/26 | 18.8 | 18.8 |
|
63.8 |
RPL06.INT.DHA.01670 |
RPL06.Interior.DHA - Control Fault Domain 4 - Install copper from GS.IDF to BMS and EPMS panels (UG from Center IDF) | Remaining Tie-ins post Mech Side Aisle install | Not Started | 11/06/26 | 12/01/26 | 18.8 | 18.8 |
|
42.5 |
RPL06.INT.DHB.01810 |
RPL06.Interior.DHB - Control Fault Domain 5 - Pull BMS from panel to devices | Remaining Tie-ins post Mech Side Aisle install | Not Started | 11/06/26 | 12/01/26 | 18.8 | 18.8 |
|
32.5 |
RPL06.INT.DHB.01820 |
RPL06.Interior.DHB - Control Fault Domain 5 - Pull EPMS from panel to devices | Remaining Tie-ins post Mech Side Aisle install | Not Started | 11/06/26 | 12/01/26 | 18.8 | 18.8 |
|
32.5 |
RPL06.INT.DHB.01830 |
RPL06.Interior.DHB - Control Fault Domain 5 - Set UPS and Panel (2) | Remaining Tie-ins post Mech Side Aisle install | Not Started | 11/06/26 | 12/01/26 | 18.8 | 18.8 |
|
17.5 |
RPL06.WP3B.015000 |
RPL06.Conn EF2<>DHB.16 Splice (A-End) Pigtails (384F) P2&3 (LV) | EF2<>DHB.16 | Not Started | 11/06/26 | 11/16/26 | 7.5 | 7.5 |
|
118.8 |
RPL06.WP3B.016440 |
RPL06.Conn EF2<>DHB.16 Install (Z-End) Pigtails (384F) P2&3 (LV) | EF2<>DHB.16 | Not Started | 11/06/26 | 11/06/26 | 1.2 | 1.2 |
|
118.8 |
RPL06.WP4.010700 |
RPL06.Conn DHB.12.05<>05 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/06/26 | 11/06/26 | 1.2 | 1.2 |
|
137.5 |
RPL06.WP4.011780 |
RPL06.Conn DHB.12.07<>07 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/06/26 | 11/06/26 | 1.2 | 1.2 |
|
138.8 |
RPL06.WP4.015060 |
RPL06.Conn DHB.14.15 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 11/06/26 | 11/20/26 | 12.5 | 12.5 |
|
113.8 |
RPL06.WP4.015080 |
RPL06.Conn DHA.03.11<>11 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/06/26 | 11/06/26 | 1.2 | 1.2 |
|
151.2 |
RPL06.WP4.015100 |
RPL06.Conn DHA.04.15<>15 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] | Jumpers | Not Started | 11/06/26 | 11/06/26 | 1.2 | 1.2 |
|
151.2 |
RPL06.WP4.015240 |
RPL06.Conn DHA.03.10<>09 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 11/06/26 | 11/12/26 | 5.0 | 5.0 |
|
138.8 |
RPL06.WP4.015260 |
RPL06.Conn DHA.04.14<>13 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] | Across-Row | Not Started | 11/06/26 | 11/12/26 | 5.0 | 5.0 |
|
138.8 |
RPL06.WP4.017020 |
RPL06.Conn DHB.13.11 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] | Jumpers (AI Confirmed) | Not Started | 11/06/26 | 11/20/26 | 12.5 | 12.5 |
|
113.8 |
GCD.RPL06.4645 |
L3/L4 Start - DHA Rows 09-16 | DH | Not Started | 11/09/26 | 11/09/26 | 0.0 | 0.0 |
|
136.2 |
GCD.RPL06.5285 |
L3/L4 Finish EY - DHC | EY | Not Started | 11/09/26 | 11/09/26 | 0.0 | 0.0 |
|
231.2 |
RPL06.CON.WP2.08860 |
RPL06.Conn - GSIDF/DH A1 - Install Cabling (Pull, Splice & terminate) | Cabling | Not Started | 11/09/26 | 11/17/26 | 7.5 | 7.5 |
|
316.2 |
RPL06.CON.WP2.08900 |
RPL06.Conn - GSIDF/DH A1 - Install Copper, WAPs, Security Camera & Access Control | Cabling | Not Started | 11/09/26 | 11/20/26 | 11.2 | 11.2 |
|
137.5 |
RPL06.CX.DHA.01080 |
RPL06.CX.DHA - L3/L4 - Elec. Domain 03/04 | DHA ELECTRICAL | Not Started | 11/09/26 | 11/13/26 | 5.0 | 5.0 |
|
45.0 |
RPL06.CX.DHA.01100 |
RPL06.CX.DHA - L3/L4 - Control Fault Domain 01 | Control Fault Domain 1 | Not Started | 11/09/26 | 12/16/26 | 31.2 | 31.2 |
|
18.8 |
RPL06.EY.ENDC.1970 |
RPL06.EY.DHD.T2 - HAC Prefab prior to install for DH C | Tent 2 | Not Started | 11/09/26 | 11/16/26 | 6.2 | 6.2 |
|
1.2 |
RPL06.INT.CTRC.2580 |
RPL06.Interior.Center-Corridor LO #10 - Install Horizontal Steel Supports for Cable Tray (IFP Add) | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/09/26 | 11/12/26 | 3.8 | 3.8 |
|
31.2 |
RPL06.INT.SSB.01590 |
RPL06.Interior.SSB - BoW - Electrical L2 Checklist Completion | Balance of Walls and OverHead | Not Started | 11/09/26 | 11/19/26 | 10.0 | 10.0 |
|
120.0 |
GCD.RPL06.3965 |
L3/L4 Finish mCUP [5-6] - RPL06 | mCup | Not Started | 11/10/26 | 11/10/26 | 0.0 | 0.0 |
|
251.2 |
GCD.RPL06.5305 |
L3 Finish - DHC | DH | Not Started | 11/10/26 | 11/10/26 | 0.0 | 0.0 |
|
231.2 |
ICM.B6.2510.C |
[SSDCB1] L3/4 Start - DHC | Commissioning | Not Started | 11/10/26 | 11/10/26 | 0.0 | 0.0 |
|
231.2 |
RPL06.CON.WP4.03400 |
RPL06.Conn WP4 FENW DHA CFD3 Infrastructure | Infrastructure | Not Started | 11/10/26 | 12/10/26 | 25.0 | 25.0 |
|
126.2 |
RPL06.CX.DHB.01400 |
RPL06.CX.DHB - L3/L4 - Control Fault Domain 03 - TW Flush and Fill | Control Fault Domain 3 | Not Started | 11/10/26 | 11/20/26 | 10.0 | 10.0 |
|
41.2 |
RPL06.CX.DHC.01030 |
RPL06.CX.DHC - L3/L4 - House Power (for electrical) | DHC HOUSE POWER | Not Started | 11/10/26 | 11/24/26 | 12.5 | 12.5 |
|
100.0 |
RPL06.INT.CTRC.01390 |
RPL06.Interior.Center-Corridor (N) - Set Equipment / Interior | Fit out (North) | Not Started | 11/10/26 | 11/17/26 | 6.2 | 6.2 |
|
56.2 |
RPL06.INT.CTRC.01410 |
RPL06.Interior.Center-Corridor (N) - Fire Life Safe Trim | Fit out (North) | Not Started | 11/10/26 | 11/16/26 | 5.0 | 5.0 |
|
72.5 |
RPL06.INT.CTRC.1660 |
RPL06.Interior.Center-Corridor - BoW - Final Paint and Tube Steel Paint (IFP Add) | Balance of Walls & Overhead | Not Started | 11/10/26 | 11/19/26 | 8.8 | 8.8 |
|
51.2 |
RPL06.INT.CTRC.2680 |
RPL06.Interior.Center-Corridor LO #10 & #12 - Install Fire Life Safety Lowside OH | Interior Leave Out Wall #10, #12 (DHB/CC) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
7.5 |
RPL06.INT.CTRC.2700 |
RPL06.Interior.Center-Corridor LO #10 & #12 - Install Plumbing Lowside OH | Interior Leave Out Wall #10, #12 (DHB/CC) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
2.5 |
RPL06.INT.CTRC.7800 |
RPL06.Interior.Center-Corridor LO #10 - Install Mechanical Piping Lowside OH & In Wall | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
60.0 |
RPL06.INT.CTRC.7820 |
RPL06.Interior.Center-Corridor LO #10 - Install Fire Life Safety Lowside OH & In Wall | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
60.0 |
RPL06.INT.CTRC.7840 |
RPL06.Interior.Center-Corridor LO #10 - Install Plumbing Lowside OH & In Wall | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
60.0 |
RPL06.INT.CTRC.7860 |
RPL06.Interior.Center-Corridor LO #10 - Install Security Lowside OH & In Wall | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
60.0 |
RPL06.INT.CTRC.7880 |
RPL06.Interior.Center-Corridor LO #10 - Install Controls / EPMS / BMS OH & In Wall | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
60.0 |
RPL06.INT.CTRC.7900 |
RPL06.Interior.Center-Corridor LO #10 - Install Electrical Lowside OH & In Wall | Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) | Not Started | 11/10/26 | 11/18/26 | 7.5 | 7.5 |
|
56.2 |
RPL06.INT.DHA.01470 |
RPL06.Conn DHA - CFD3 - Set Passive Racks for WP#3b (16) | Infrastructure | Not Started | 11/10/26 | 11/13/26 | 3.8 | 3.8 |
|
73.8 |