Activity ID Activity Name WBS Status Start Finish Dur (d) Rem (d) % Comp Float (d)
RPL06.INT.CTRC.3000 RPL06.Interior.Center-Corridor LO #10 & #12 - Install Electrical Lowside OH Interior Leave Out Wall #10, #12 (DHB/CC) Not Started 11/19/26 11/24/26 5.0 5.0
0%
2.5
RPL06.INT.CTRC.3600 RPL06.Interior.Center-Corridor LO #11 & #13 - Install Mechanical Piping Lowside OH Interior Leave Out Wall #11, #13 (DHA/CC) Not Started 11/19/26 11/23/26 3.8 3.8
0%
-10.0
RPL06.INT.CTRC.7960 RPL06.Interior.Center-Corridor LO #10 - Backing Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 11/19/26 11/20/26 2.5 2.5
0%
56.2
RPL06.WP3B.012140 RPL06.Conn EF2<>DHB.17 Pull Pigtails (384F) P2&3 (LV) EF2<>DHB.17 Not Started 11/19/26 11/19/26 1.2 1.2
0%
55.0
RPL06.WP3B.014080 RPL06.Conn EF1<>DHA.06 Splice (A-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.06 Not Started 11/19/26 11/30/26 7.5 7.5
0%
121.2
RPL06.WP3B.015520 RPL06.Conn EF1<>DHA.06 Install (Z-End) Pigtails (384F) P1&4 (LV) EF1<>DHA.06 Not Started 11/19/26 11/19/26 1.2 1.2
0%
121.2
RPL06.WP4.016520 RPL06.Conn DHA.01.04 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/19/26 12/04/26 12.5 12.5
0%
128.8
RPL06.WP4.016540 RPL06.Conn DHA.02.08 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/19/26 12/04/26 12.5 12.5
0%
128.8
RPL06.WP4.016560 RPL06.Conn DHB.17 Pull Ext. Trunk (384F) [SSW<>JXSW] SSW<>JXSW Not Started 11/19/26 11/19/26 1.2 1.2
0%
117.5
RPL06.WP4.016580 RPL06.Conn DHB.18 Pull Ext. Trunk (384F) [SSW<>JXSW] SSW<>JXSW Not Started 11/19/26 11/19/26 1.2 1.2
0%
117.5
RPL06.WP4.016840 RPL06.Conn DHB.17.25 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/19/26 12/04/26 12.5 12.5
0%
78.8
RPL06.WP4.016860 RPL06.Conn DHB.18.29 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/19/26 12/04/26 12.5 12.5
0%
78.8
RPL06.WP4.016920 RPL06.Conn DHA.03.12<>11 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/19/26 11/19/26 1.2 1.2
0%
138.8
RPL06.WP4.016940 RPL06.Conn DHA.04.16<>15 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/19/26 11/19/26 1.2 1.2
0%
138.8
RPL06.WP4.017400 RPL06.Conn DHB.17 Pull Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 11/19/26 11/19/26 1.2 1.2
0%
107.5
RPL06.WP4.017420 RPL06.Conn DHB.18 Pull Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 11/19/26 11/19/26 1.2 1.2
0%
107.5
RPL06.CON.WP2.09120 RPL06.Conn - CorpNet & FacNet Available (DH A) - all IDFS WP#02 GS Not Started 11/20/26 11/20/26 0.0 0.0
0%
315.0
RPL06.CON.WP3B.01320 RPL06.Conn EF2<>DHB.18 - WBS Summary EF2<>DHB.18 Not Started 11/20/26 12/07/26 12.5 12.5
0%
105.0
RPL06.Conn.MS.01020 RPL06.Conn Wifi Ready - DH A (Pred from RPL10 CorpNet needed?) Connectivity Milestones Not Started 11/20/26 11/20/26 0.0 0.0
0%
137.5
RPL06.INT.CTRC.1760 RPL06.Interior.Center-Corridor - BoW - Install Flooring Tiles/Resinous Flooring in specific rooms Balance of Walls & Overhead Not Started 11/20/26 12/02/26 8.8 8.8
0%
51.2
RPL06.INT.CTRC.3580 RPL06.Interior.Center-Corridor LO #11 - Install Remaining Vertical Tube Steel Support for Cable Tray (IFP Add) Remaining of LO Wall #11 (Spoke Parts) Not Started 11/20/26 11/23/26 2.5 2.5
0%
18.8
RPL06.INT.DHC.02310 RPL06.Interior.DHC - OFE - Control Fault Domain 1 (Mech Side Aisle) Control Fault Domain 1 Not Started 11/20/26 12/08/26 13.8 13.8
0%
8.8
RPL06.INT.DHD.02350 RPL06.Interior.DHD - OFE - Control Fault Domain 2 (HAC) Control Fault Domain 2 Not Started 11/20/26 12/07/26 12.5 12.5
0%
12.5
RPL06.INT.SSBC.01520 RPL06.Interior.SSB-Corridor - Remaining Mechanical DHA OFE TIe Ins Fit out Not Started 11/20/26 11/30/26 6.2 6.2
0%
117.5
RPL06.INT.SSBC.01540 RPL06.Interior.SSB-Corridor - Remaining Electrical DHA OFE TIe Ins Fit out Not Started 11/20/26 11/30/26 6.2 6.2
0%
117.5
RPL06.WP3B.012160 RPL06.Conn EF2<>DHB.18 Pull Pigtails (384F) P2&3 (LV) EF2<>DHB.18 Not Started 11/20/26 11/20/26 1.2 1.2
0%
55.0
RPL06.WP3B.013580 RPL06.Conn EF2<>DHB.17 Install (A-End) Pigtails (384F) P2&3 (LV) EF2<>DHB.17 Not Started 11/20/26 11/20/26 1.2 1.2
0%
106.2
RPL06.WP4.016880 RPL06.Conn DHB.17 Pull Trunk (192F) [FSW<>SSW] FSW<>SSW Not Started 11/20/26 11/20/26 1.2 1.2
0%
117.5
RPL06.WP4.016900 RPL06.Conn DHB.18 Pull Trunk (192F) [FSW<>SSW] FSW<>SSW Not Started 11/20/26 11/20/26 1.2 1.2
0%
117.5
RPL06.WP4.017120 RPL06.Conn DHA.05.17<>17 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/20/26 11/20/26 1.2 1.2
0%
138.8
RPL06.WP4.017140 RPL06.Conn DHA.06.21<>21 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/20/26 11/20/26 1.2 1.2
0%
138.8
RPL06.WP4.017260 RPL06.Conn DHA.05.19<>19 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/20/26 11/24/26 3.8 3.8
0%
123.8
RPL06.WP4.017280 RPL06.Conn DHA.06.23<>23 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/20/26 11/24/26 3.8 3.8
0%
123.8
RPL06.WP4.017600 RPL06.Conn DHB.17.25<>25 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/20/26 11/24/26 3.8 3.8
0%
107.5
RPL06.WP4.017620 RPL06.Conn DHB.17 Install Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 11/20/26 11/24/26 3.8 3.8
0%
126.2
RPL06.WP4.017640 RPL06.Conn DHB.18 Install Ext. Trunk (24F) [PON (Passive, In-Rack)] In-Rack Not Started 11/20/26 11/24/26 3.8 3.8
0%
126.2
RPL06.WP4.017660 RPL06.Conn DHB.18.30<>29 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/20/26 11/25/26 5.0 5.0
0%
107.5
RPL06.CX.DHB.01500 RPL06.CX.DHB - L3/L4 - Control Fault Domain 05 - FW Flush and Fill Control Fault Domain 5 Not Started 11/23/26 12/03/26 8.8 8.8
0%
42.5
RPL06.INT.CTRC.01440 RPL06.Interior.Center-Corridor (N) - Plumbing Trim Fit out (North) Not Started 11/23/26 11/30/26 5.0 5.0
0%
72.5
RPL06.INT.CTRC.01750 RPL06.Interior.Center-Corridor (S) - Fire Life Safe Trim Fit out (South) Not Started 11/23/26 11/30/26 5.0 5.0
0%
38.8
RPL06.INT.CTRC.01970 RPL06.Interior.Center-Corridor (S) - Set Equipment / Interior Fit out (South) Not Started 11/23/26 12/01/26 6.2 6.2
0%
30.0
RPL06.INT.CTRC.06960 RPL06.Interior.Center-Corridor - Final Finishes & Fixtures - MEP Trims Restrooms Not Started 11/23/26 12/03/26 8.8 8.8
0%
41.2
RPL06.INT.CTRC.06980 RPL06.Interior.Center-Corridor - Final Finishes & Fixtures - Install Tile/ Grout Restrooms Not Started 11/23/26 12/08/26 12.5 12.5
0%
37.5
RPL06.INT.CTRC.07000 RPL06.Interior.Center-Corridor - Final Finishes & Fixtures - Install Fixtures, Partitions & Accessories Restrooms Not Started 11/23/26 12/03/26 8.8 8.8
0%
41.2
RPL06.INT.CTRC.1800 RPL06.Interior.Center-Corridor - BoW - Install Door (Verify with Trades before installation) Balance of Walls & Overhead Not Started 11/23/26 12/03/26 8.8 8.8
0%
50.0
RPL06.INT.CTRC.8280 RPL06.Interior.Center-Corridor LO #10 - Install Door Frame Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 11/23/26 11/24/26 2.5 2.5
0%
56.2
RPL06.INT.CTRC.8360 RPL06.Interior.Center-Corridor LO #11 - Install Security Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 11/23/26 11/25/26 3.8 3.8
0%
52.5
RPL06.INT.CTRC.8380 RPL06.Interior.Center-Corridor LO #11 - Install Controls / EPMS / BMS OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 11/23/26 11/25/26 3.8 3.8
0%
52.5
RPL06.INT.CTRC.8400 RPL06.Interior.Center-Corridor LO #11 - Install Fire Life Safety Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 11/23/26 11/25/26 3.8 3.8
0%
52.5
RPL06.INT.CTRC.8420 RPL06.Interior.Center-Corridor LO #11 - Install Plumbing Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 11/23/26 11/25/26 3.8 3.8
0%
52.5
RPL06.INT.CTRC.8440 RPL06.Interior.Center-Corridor LO #11 - Install Mechanical Piping Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 11/23/26 11/25/26 3.8 3.8
0%
52.5
RPL06.INT.CTRC.8460 RPL06.Interior.Center-Corridor LO #11 - Install Electrical Lowside OH & In Wall Remaining of LO Wall #11 (Spoke Parts) Not Started 11/23/26 12/02/26 7.5 7.5
0%
48.8
RPL06.INT.DHA.01720 RPL06.Interior.DHA - Control Fault Domain 5 - Pull BMS from panel to devices Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/15/26 18.8 18.8
0%
40.0
RPL06.INT.DHA.01730 RPL06.Interior.DHA - Control Fault Domain 5 - Pull EPMS from panel to devices Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/15/26 18.8 18.8
0%
40.0
RPL06.INT.DHA.01740 RPL06.Interior.DHA - Control Fault Domain 5 - Set UPS and Panel (2) Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/15/26 18.8 18.8
0%
13.8
RPL06.INT.DHB.01990 RPL06.Interior.DHB - Control Fault Domain 5 - L2 Checklist Completion Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/15/26 18.8 18.8
0%
26.2
RPL06.INT.DHD.01170 RPL06.Interior.DHD - Control Fault Domain 1 - Pull BMS from panel to devices Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/22/26 25.0 25.0
0%
48.8
RPL06.INT.DHD.01180 RPL06.Interior.DHD - Control Fault Domain 1 - Pull EPMS from panel to devices Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/22/26 25.0 25.0
0%
48.8
RPL06.INT.DHD.01190 RPL06.Interior.DHD - Control Fault Domain 1 - Set UPS and Panel (2) Remaining Tie-ins post Mech Side Aisle install Not Started 11/23/26 12/22/26 25.0 25.0
0%
36.2
RPL06.INT.ENDC.1960 RPL06.Interior.End-Corridor - BoW - Install Horizontal Steel for Cable Tray (IFP Add) Balance of Walls & Overhead Not Started 11/23/26 11/30/26 5.0 5.0
0%
131.2
RPL06.WP3B.013600 RPL06.Conn EF2<>DHB.18 Install (A-End) Pigtails (384F) P2&3 (LV) EF2<>DHB.18 Not Started 11/23/26 11/23/26 1.2 1.2
0%
105.0
RPL06.WP3B.015020 RPL06.Conn EF2<>DHB.17 Splice (A-End) Pigtails (384F) P2&3 (LV) EF2<>DHB.17 Not Started 11/23/26 12/02/26 7.5 7.5
0%
106.2
RPL06.WP3B.016460 RPL06.Conn EF2<>DHB.17 Install (Z-End) Pigtails (384F) P2&3 (LV) EF2<>DHB.17 Not Started 11/23/26 11/23/26 1.2 1.2
0%
106.2
RPL06.WP4.017040 RPL06.Conn DHB.17 Pull Trunk (384F) [RSW<>FSW] Trunks Not Started 11/23/26 11/23/26 1.2 1.2
0%
117.5
RPL06.WP4.017060 RPL06.Conn DHB.18 Pull Trunk (384F) [RSW<>FSW] Trunks Not Started 11/23/26 11/23/26 1.2 1.2
0%
117.5
RPL06.WP4.017380 RPL06.Conn DHB.14.16 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/23/26 12/08/26 12.5 12.5
0%
113.8
RPL06.WP4.017520 RPL06.Conn DHB.15.20<>19 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/23/26 11/23/26 1.2 1.2
0%
123.8
RPL06.WP4.017540 RPL06.Conn DHB.16.24<>23 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/23/26 11/23/26 1.2 1.2
0%
123.8
RPL06.WP4.019140 RPL06.Conn DHB.13.12 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/23/26 12/08/26 12.5 12.5
0%
113.8
GCD.RPL06.2608 L3/L4 Start - DHB Rows 25-32 DH Not Started 11/24/26 11/24/26 0.0 0.0
0%
111.2
RPL06.CX.DHB.01130 RPL06.CX.DHB - L3/L4 - Elec. Domain 07/08 DHB ELECTRICAL Not Started 11/24/26 12/01/26 5.0 5.0
0%
35.0
RPL06.INT.CTRC.3620 RPL06.Interior.Center-Corridor LO #11 & #13 - Install Fire Life Safety Lowside OH Interior Leave Out Wall #11, #13 (DHA/CC) Not Started 11/24/26 11/30/26 3.8 3.8
0%
-5.0
RPL06.INT.CTRC.3640 RPL06.Interior.Center-Corridor LO #11 & #13 - Install Plumbing Lowside OH Interior Leave Out Wall #11, #13 (DHA/CC) Not Started 11/24/26 11/30/26 3.8 3.8
0%
-10.0
RPL06.INT.CTRC.3720 RPL06.Interior.Center-Corridor LO #11 - Install Remaining Horizontal Steel Supports for Cable Tray (IFP Add) Remaining of LO Wall #11 (Spoke Parts) Not Started 11/24/26 11/30/26 3.8 3.8
0%
18.8
RPL06.INT.SBC.04020 RPL06.Interior.SSB-Corridor - BoW - Mechanical L2 Checklist Completion Balance of Walls & Overhead Not Started 11/24/26 12/09/26 12.5 12.5
0%
63.8
RPL06.WP3B.015040 RPL06.Conn EF2<>DHB.18 Splice (A-End) Pigtails (384F) P2&3 (LV) EF2<>DHB.18 Not Started 11/24/26 12/03/26 7.5 7.5
0%
105.0
RPL06.WP3B.016480 RPL06.Conn EF2<>DHB.18 Install (Z-End) Pigtails (384F) P2&3 (LV) EF2<>DHB.18 Not Started 11/24/26 11/24/26 1.2 1.2
0%
105.0
GCD.RPL06.5705 Area Completion - mCup mCUP Not Started 11/25/26 11/25/26 0.0 0.0
0%
286.2
RPL06.CX.DHC.01060 RPL06.CX.DHC - L3/L4 - House Power (for mechainical) DHC HOUSE POWER Not Started 11/25/26 12/10/26 12.5 12.5
0%
126.2
RPL06.EY.SSB.01280 RPL06.EY.SSB - Install Curb and Gutter Hardscape and Landscape Not Started 11/25/26 12/10/26 12.5 12.5
0%
68.8
RPL06.INT.CTRC.2780 RPL06.Interior.Center-Corridor LO #10 & #12 - Install Door Frames Interior Leave Out Wall #10, #12 (DHB/CC) Not Started 11/25/26 11/30/26 2.5 2.5
0%
2.5
RPL06.INT.CTRC.7980 RPL06.Interior.Center-Corridor LO #10 - QC Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 11/25/26 11/25/26 1.2 1.2
0%
58.8
RPL06.INT.CTRC.8240 RPL06.Interior.Center-Corridor LO #10 - Fire Safing/ Wall Finishes Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 11/25/26 11/30/26 2.5 2.5
0%
56.2
RPL06.INT.DHD.02370 RPL06.Interior.DHD - OFE - Control Fault Domain 2 (Mech Side Aisle) Control Fault Domain 2 Not Started 11/25/26 12/08/26 10.0 10.0
0%
17.5
RPL06.INT.SSB.14680 RPL06.Interior.SSB LO #01 to #05 - Final Clean Finishes Not Started 11/25/26 12/02/26 5.0 5.0
0%
72.5
RPL06.WP4.017720 RPL06.Conn DHA.05.19<>19 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/25/26 11/25/26 1.2 1.2
0%
136.2
RPL06.WP4.017740 RPL06.Conn DHA.06.23<>23 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/25/26 11/25/26 1.2 1.2
0%
136.2
RPL06.WP4.017880 RPL06.Conn DHA.05.18<>17 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/25/26 12/02/26 5.0 5.0
0%
123.8
RPL06.WP4.017900 RPL06.Conn DHA.06.22<>21 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/25/26 12/02/26 5.0 5.0
0%
123.8
RPL06.WP4.018080 RPL06.Conn DHB.17.25<>25 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/25/26 11/25/26 1.2 1.2
0%
122.5
RPL06.WP4.018140 RPL06.Conn DHB.17.27<>27 Pull Simplex Jumper (SC<>LC) [PON (Active, In-Row)] Jumpers Not Started 11/25/26 12/01/26 3.8 3.8
0%
107.5
RPL06.CX.DHA.01400 RPL06.CX.DHA - L3/L4 - Control Fault Domain 03 - TW Flush and Fill Control Fault Domain 3 Not Started 11/30/26 12/09/26 10.0 10.0
0%
47.5
RPL06.INT.CTRC.8000 RPL06.Interior.Center-Corridor LO #10 - Hang Drywall Remaining of LO Wall #10 (Spoke Parts & Spoke Tech) Not Started 11/30/26 12/03/26 5.0 5.0
0%
58.8
RPL06.WP3B.016940 RPL06.Conn EF1<>DHA.05 Test Pigtails (384F) P1&4 (LV) EF1<>DHA.05 Not Started 11/30/26 12/01/26 2.5 2.5
0%
75.0
RPL06.WP4.017680 RPL06.Conn DHA.03.11 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/30/26 12/11/26 12.5 12.5
0%
110.0
RPL06.WP4.017700 RPL06.Conn DHA.04.15 Pull Duplex Jumper (LC<>LC) [RSW<>FSW (AI Confirmed)] Jumpers (AI Confirmed) Not Started 11/30/26 12/11/26 12.5 12.5
0%
110.0
RPL06.WP4.018200 RPL06.Conn DHB.18.30<>29 Install (A-End) Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/30/26 11/30/26 1.2 1.2
0%
121.2
RPL06.WP4.018260 RPL06.Conn DHB.18.32<>31 Pull Simplex Jumper (SC<>LC) [PON (Active, Across-Row)] Across-Row Not Started 11/30/26 12/03/26 5.0 5.0
0%
107.5
RPL06.CX.SSB.01000 RPL06.CX.SSB - L3, L4, IST - WBS Summary SSB Not Started 12/01/26 02/26/27 75.0 75.0
0%
210.0
RPL06.CX.SSB.01010 RPL06.CX.SSB - L3 SSB Not Started 12/01/26 01/21/27 43.8 43.8
0%
210.0